Parameter | Description |
No. |
|
P540 | Memory Fault Alarm |
| If the control unit detects a memory fault |
P541 | PV Out of Limits |
| If the Pv is out of limits then an alarm can be reported by |
| a relay, current output or by both |
P542 | Current Saturated |
| If the current is saturated is out of limits then an alarm |
| can be reported by a relay, current output or by both |
P543 | Temperature Out of Limits |
| If the temperature is out of limits then an alarm can be |
| reported bya relay, current output or by both |
P545 | Digital Input 1 Active |
P570 | Display Select 1 (upper) |
| This parameter designates what is shown on the upper |
| display and can be selected from a list (PV, %, clock) |
P571 | Display Select 2 (mid) |
| This parameter designates what is shown on the mid |
| display and can be selected from a list (PV, %, clock) |
P572 | Display Select 3 (lower) |
| This parameter designates what is shown on the lower |
| display and can be selected from a list (PV, %, clock) |
P575 | Backlight On/Off |
P630 | Set Frequency of Operation |
| High, Low or Auto |
P640 | Min dB |
P641 | Max dB |
P642 | Sensor Dirty Threshold |
| A user alterable value in dBs.The control unit |
| compares successive zero calibrations and if the |
| difference exceeds this value then the control unit |
| displays the warning 'CHECK SENSOR CLEAN'. |
P700 | 4mA output adjust |
| Factory calibrated. The user can adjust the 4mA output |
| via the up down arrows |
P701 | 20mA output adjust |
| Factory calibrated. The user can adjust the 20mA output |
| via the up down arrows |
P702 | Set Current |
| Force current to a value to check loop equipment |
P730 | Date |
P731 | Time |
Min. | Max. | Default | |
value | value |
| |
0 | 3 | both | |
0 | 3 | both | |
0 | 3 | none | |
0 | 3 | none | |
- | - | - |
|
1 | - | - | Time |
1 | - | - | PV |
1 | - | - | bar graph |
- | - | - |
|
- | - | - |
|
- | - | - |
|
- | - | - |
|
0 | - | 0 |
- | - | 735 |
- | - | 3194 |
- | - | 0 |
- | - | - |
- | - | - |