1.2Modes of Operation

Introduction

1.2Modes of Operation

1.2.1Normal Mode

Operating in normal mode, the Liebert NX’s rectifier derives power from a utility AC source and supplies regulated DC power to the inverter, which regenerates precise AC power to supply the connected equipment. The rectifier also uses the utility source power to charge the DC sources.

1.2.2Bypass Mode

When the Liebert NX is in bypass mode, the load is directly supported by utility power and is without DC source backup protection.

The Liebert NXs inverter and bypass static switch will shift the load from the inverter to bypass mode without an interruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:

Inverter fails

Inverter overload capacity is exceeded

Inverter is manually turned Off by the user

NOTE

If the inverter is asynchronous with the bypass, the static switch will transfer the load from the inverter to the bypass WITH interruption in AC power to the critical load. This interruption will be less than 10ms. This interruption time may be altered by modifying the Output transfer interrupt time setting.

1.2.3Battery Mode

When utility AC power fails, the Liebert NX protects the critical load by instantaneously channeling DC source power to the inverter, which continues supporting the critical load without interruption.

When utility power returns and is within acceptable limits, the Liebert NX automatically shifts back to Normal mode, with the rectifier powering the critical load.

1.2.4Maintenance Bypass

The installation of a Maintenance Bypass Cabinet or Assembly is recommended to allow you to totally isolate the UPS from all power sources. Use of the Maintenance Bypass is described in 2.0 - Operation.