Emerson NX manual Electrical specifications, Physical specifications, Specifications

Models: NX

1 48
Download 48 pages 62.08 Kb
Page 45
Image 45
Electrical specifications

Specifications

Table 8

Electrical specifications

 

 

 

Input Parameters

 

 

Input Voltage to Rectifier, VAC, 3-phase, 3-wire

480V

 

Input Voltage to Bypass, VAC, 3-phase, 3-wire

480V

 

Input Voltage Range, VAC

+10% to -30%

 

Input Frequency, Hz

60

 

Permissible Input Frequency Range, Hz

55-65

 

Rectifier Power Walk-In, sec

1-90 (selectable) in 1 Sec. Increments

DC Parameters

 

 

Battery Type

VRLA (Valve Regulated Lead Acid)

 

or FLA (Flooded Lead Acid)

 

 

 

DC Bus Range, VDC

396-600

 

DC Float Voltage, VPC

2.27

 

End-Cell Voltage, VPC

1.65 (for VRLA / FLA)

DC Ripple Voltage in Float and Const V Ch. mode, %

<1 (RMS Value) < 3.4% Vpp

Output Parameters

 

 

Output Voltage, 3-phase, 3-wire

480V

 

Output Voltage Regulation, %

< 1% (3-Phase RMS Average)

 

Output Frequency, Hz

60

 

Output Frequency Regulation, %

± 0.1

 

Capacity to Handle Step Load, %

0-100 or 100-0

 

Voltage Displacement, ° el

120° ±1° el (With Unbalanced Load)

 

Compliance to FCC Class-A

Standard

Table 9

Physical specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert NX Model Size

225

 

250

 

300

 

400

 

500

600

Physical Parameters and Standards, in (mm)

 

 

 

 

 

 

 

 

 

 

 

Width

 

53.4

 

 

 

 

 

90.7

 

 

Depth

 

 

 

 

 

33.7

 

 

 

 

Height

 

 

 

 

 

78.6

 

 

 

Weight, Unpackaged, approximate, lb. (kg)

 

2,450 (1,110)

 

 

4450 lb. (2019kg)

Maximum Heat Dissipation, Full Load, BTU/hr

41,000

 

45,000

 

54,000

 

72,000

 

90,000

108000

Color

 

 

 

 

 

Black (ZP-7021)

 

 

Front Door Opening (for serviceability)

 

 

 

 

More than 90°

 

 

Degree of Protection for UPS Enclosure

 

 

IP 20 (with and without front door open)

 

Minimum Clearance, Top, In. (mm)

 

 

 

 

24in (610mm)

 

 

Minimum Clearance, Back, In. (mm)

 

 

 

 

 

0

 

 

 

Minimum Clearance, Sides, In. (mm)

 

 

 

 

 

0

 

 

 

Location of Cable Entrance

 

 

 

 

Top or Bottom

 

 

 

 

 

 

 

 

UL, 1778, 4th Ed.

 

 

 

 

 

 

 

 

CSA 22.2 107.3

 

 

 

 

 

 

 

FCC Part 15, Class A

 

 

 

 

 

 

IEC62040-2, Level 4, Criteria A

 

 

 

 

 

EN61000-4-3, Level 3, Criteria A

 

Standards & Conformities

 

 

EN61000-4-6, Level 4, Criteria A

 

 

 

 

 

EN61000-2-2, Criteria A

 

 

 

 

 

EN61000-4-4, Level 4, Criteria A

 

 

 

 

 

ANSI C62.41, Category A3 &B3

 

 

 

 

 

 

 

ISTA Procedure 1H

 

 

 

 

 

 

 

 

WEEE

 

 

39

Liebert®NX

Page 45
Image 45