2.4.2Input Power Failure—Load on DC Source

Operation

2.4.2Input Power Failure—Load on DC Source

If the utility AC power source fails or is outside the acceptable range, the DC source becomes the power source for the UPS module inverters. The UPS continues to supply power to the critical load and also to the UPS controls.

Use the Battery Time screen at the UPS modules to monitor the present DC source voltage compared to the shutdown value. The time the DC source can sustain the load depends on the size of the load and the size and condition of the DC source.

The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the current in amperes.

Figure 16 Input power fail, load on DC source

Module Bypass

 

AC Input

 

 

BFB

Module Rectifier

DC

AC Input

 

Bus

UPS Module

 

 

 

UPS Output

 

Critical

 

 

 

 

 

 

 

 

 

Load

To DC Supply

2.4.3Off DC Source

The DC source can be disconnected from the UPS, if required for maintenance, by opening the module battery disconnect (MBD) circuit breaker. In this situation, the UPS module will continue to supply conditioned power to the critical load, but if input power fails, the UPS system cannot supply power to the load.

NOTICE

Risk of unexpected power loss to the connected load. Can cause equipment damage.

When the UPS is operating with the module battery disconnect (MBD) circuit breaker(s) open, the critical load is not protected from loss of the utility source power.

Figure 17 Load on UPS, DC source not available

Module Bypass

 

AC Input

 

 

BFB

Module Rectifier

DC

AC Input

 

Bus

UPS Module

UPS Output Critical

Load

To DC Supply

Liebert®NX

16

Page 22
Image 22
Emerson NX manual Input Power Failure-Load on DC Source, Off DC Source, Input power fail, load on DC source