Options

3.3Manage UPS Adapter

ManageUPS NET Adapter III offers an open approach to network power management by delivering a complete set of manageability options including: WEB, Telne and Out-Of-Band accessibility, in addition to the full-featured, embedded SNMP agent. Event messages are also available as e-mail and SNMP Traps - a truly versatile tool for managing Liebert NX UPS systems in a network environment.

The software features:

DHCP Network Configuration—Supports automatic IP settings configuration using the DHCP protocol. The DHCP server must be located on a network that is accessible from the LAN that ManageUPS-II is connected to.

Multiple Network Access Methods—Site power and UPS status information can be accessed securely from any computer on your network. View UPS system status in real time for situational decision support. Access via Telnet, SNMP, or Web Browser. SNMP Agent conforms to RFC1628 Standard UPS MIB.

Network Shutdown—ManageUPS includes a UPS status server and a network shutdown controller. Use these features with host shutdown software (RCCMD, MopUPS NSA, MopUPS Professional or MopUPS P/R) to ensure safe shutdown of multiple servers, workstations or PCs in TCP/IP network environments.

Event and Data Logging—ManageUPS II keeps a log file of UPS events and environment data. On-board log file viewer lets you filter records for easy analysis.

For details, see http://connectivity.Emersonpower.com/

3.4Connectivity

Table 3 gives details of the various combinations of connectivity solutions that can be used with the Liebert NX. Only one of the combinations may be used at a time. Other combinations may be possible. For further information, see http://connectivity.Emersonpower.com/ The following interfaces can be found on the Liebert NX:

Table 3

Connectivity combinations

 

 

 

 

Interface

Description

Input/Output/Serial/CAN

XS3

Slot available for use with a connectivity option, typically ManageUPS

Serial

NET III Adapter

 

 

XS6

Slot for the LIFE.net slot modem

Serial

 

 

 

X3

Standard serial interface RS232 COM - female –

Serial

Available, if XS3 slot is empty or MUN III card is installed

 

 

 

Standard serial interface RS-232 COM for external LIFE.net kit (e.g.

 

X6

LIFE.net, GSM modem) only is XS6 is empty - male - Not available, if a

Serial

 

XS6 slot modem is installed

 

X19

2x15-pole screw connector for parallel UPS connection

 

 

 

 

X20

RJ45 interface for synchronization with external signal

 

 

 

 

TB1

16-pole screw connector for input contacts (see 3.4.1 - Available

Input

Selectable Input Contacts)

 

 

TB2

16-pole screw connector for output contacts (see 3.4.2 - Available

Output

Selectable Output Contacts)

 

 

XT 3/8

4-pole screw for EPO input and output

Input and Output

 

 

 

XT1

External battery temperature sensor connection

Input

 

 

 

TB3

Battery Interface and SKRU Key Status

Input and Output

 

 

 

TB4

SKRU Enable Status

Input and Output

 

 

 

Liebert®NX

28

Page 34
Image 34
Emerson NX manual Manage UPS Adapter, Connectivity combinations