Options

3.4.1Available Selectable Input Contacts

•On Gen

•Fast Power Off

•MBB Aux Contacts

•Start battery test (see Note 4 below)

•Fault acknowledge

•Bypass and Inverter both Off

•Stop battery test (see Note 4 below)

Notes

1.Each signal can be inverted

2.Each signal can have a turn-on delay applied from 0-60 seconds

3.Each signal can have a turn-off delay applied from 0-60 seconds

4.To guarantee that the command is accepted, keep the function active at least 10/15 seconds.

3.4.2Available Selectable Output Contacts

• Summary Alarm (fault/warning)

• Inverter Not On

•

Residual Battery Autonomy is Expiring

•

Rectifier or Bypass Mains Failure

•

Inverter On

•

Load Supplied by battery

•

Bypass Active (AS400-like)

•

Maintenance Bypass Switch Closed

• Inverter Operation, Self Clocked

• Shutdown Command Pending

• Summary Fault

• Inverter Stopped Due to Fault

•

Bypass Stopped Due to Fault

•

Rectifier Fault

• Summary Warning

• Inverter Over Temperature warning

• Imminent Shutdown

• Battery Undervoltage

•

Inverter Overload

•

Rectifier or Bypass Mains Failure

•

Rectifier Mains Failure

•

Bypass Mains Failure

• Battery Overtemperature

• SGS on (Standby Generator Set)

• Battery Prewarning Level

• Battery Capacity @ 25%

• Load @ 25%

• Battery Capacity @ 50%

• Load @ 50%

• Battery Capacity @ 75%

• Load @ 75%

• Battery Capacity @ 100%

• Load @ 100%

• Line Fault

• Load @ 105%

• Summary Alarm OR Line Fault

• Power Loss Prewarning

• Power Loss Alarm

•

Backfeed Fault

 

 

Notes

1.Each signal can be inverted

2.Each signal can have a turn-on delay applied from 0 to 60 seconds

3.Each signal can have a turn-off delay applied from 0 to 60 seconds