Maintenance
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and tighten if necessary. NOTE that when installing a new battery, the initial torque value is 5
Table 6 Battery retorque values
|
| Retorque Value | ||
Battery Mfr. | Battery Model # |
| ||
|
|
|
| |
| 110 | (12.4) | ||
|
|
|
| |
| 110 | (12.4) | ||
|
|
|
| |
C&D | 110 | (12.4) | ||
|
|
|
| |
| 110 | (12.4) | ||
|
|
|
| |
| 110 | (12.4) | ||
|
|
|
| |
| 65 | (7.3) | ||
|
|
|
| |
| 65 | (7.3) | ||
|
|
|
| |
| 65 | (7.3) | ||
|
|
|
| |
Enersys | 65 | (7.3) | ||
|
|
| ||
65 | (7.3) | |||
| ||||
|
|
|
| |
| 65 | (7.3) | ||
|
|
|
| |
| 16HX800F | 100 | (11.3) | |
|
|
|
| |
| 16HX925F | 100 | (11.3) | |
|
|
|
| |
| 24HR3000 | 65 | (7.3) | |
|
|
|
| |
East Penn | 27HR3500 | 65 | (7.3) | |
|
|
| ||
31HR4000 | 65 | (7.3) | ||
| ||||
|
|
|
| |
| 31HR5000 | 65 | (7.3) | |
|
|
|
|
If the system uses a different model battery, contact Liebert Services for the required torque value.
To access battery cell terminals, disconnect the
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and insulate the cables connected to the battery. Secure each battery shelf with retaining screws when maintenance is complete.
Other DC Sources
If the UPS system uses a DC source other than a
Liebert®NX™ | 36 |