Emerson ROC827 instruction manual Select Configuration I/O AI Points

Models: ROC827

1 140
Download 140 pages 44.65 Kb
Page 118
Image 118

 

 

ROC827 Instruction Manual

 

 

Failure to exercise proper electrostatic discharge precautions, such as

 

Caution

 

wearing a grounded wrist strap may reset the processor or damage

 

 

electronic components, resulting in interrupted operations.

1.Connect a multimeter across the scaling resistor connected to the + and COM terminals of the module and set the multimeter to measure voltage.

2.Connect to ROCLINK 800 software.

3.Select Configuration > I/O > AI Points.

4.Select the correct Analog Input Point Number.

5.Verify the following readings:

ƒWhen the Value is –25% of span as configured in Table 6-1, it is an indication of no current flow (0 mA), which can result from open field wiring or a faulty field device. The multimeter should show 0 (zero) Volts dc.

ƒWhen the Value is in excess of 100% of span as configured in Table 6-1, it is an indication of maximum current flow, which can result from shorted field wiring or a faulty field device. The multimeter should show 5 Volts dc.

ƒWhen the Value is between the Low Reading EU and the High Reading EU, verify the accuracy of the reading by measuring the voltage across the terminals with the multimeter.

6.Convert this reading to the Value value:

Value = [((Vmultimeter – 1) 4) * Span] + Low Reading EU

where Span = High Reading EU – Low Reading EU.

Note: This calculated value should be within one-tenth of one percent of the Filter value measured by the ROC827.

7.Verify the accuracy by reading the loop current with a multimeter, setting the multimeter to measure current in mA, and connecting it in series with current loop. Be sure to take into account that input values can change rapidly, which can cause a greater error between the measured value and the calculated value.

8.Calculate the Value from the mAmp reading of the multimeter:

Value = [((mAmpmultimeter* Rscaling resistor – 1) * 4) * Span] + Low

Reading EU

where Span = High Reading EU – Low Reading EU and Rscaling resistor should be 250 ohms (factory installed scaling resistor value).

Note: If the calculated value and the measured value are the same, the

AI module is operating correctly.

Issued Mar-06

Troubleshooting

6-6

Page 118
Image 118
Emerson ROC827 instruction manual Select Configuration I/O AI Points, Value = Vmultimeter 1 ⎟ 4 * Span + Low Reading EU