ROC827 Instruction Manual

3.5.3 Replacing the Internal Battery

The internal Sanyo 3 volt CR2430 lithium backup battery located on the CPU provides backup of the data and the Real-Time Clock when the main power is not connected. The battery has a one-year minimum backup life while the battery is installed and no power is applied to the ROC827. The battery has a ten-year backup life while the backup battery is installed and power is applied to ROC827 or when the battery is removed from the ROC827.

Recommended replacement Lithium/Manganese Dioxide batteries include:

Table 3-17. Replacement Battery Types

Part

Battery, Lithium, 3V

Size

24 mm (0.94 in) diameter x 3 mm (0.12 in) height

Type

Coin Type

Capacity

280 mAh minimum

Acceptable Types

ƒ

Duracell DL2430

 

ƒ

Eveready CR2430

 

ƒ

Sanyo CR2430

 

ƒ

Varta CR2430

Note: Remove the internal backup battery if you intend to store the

ROC827 for an extended period.

Caution

When working on units located in a hazardous area (where explosive

gases may be present), make sure the area is in a non-hazardous state

 

before performing these procedures. Performing these procedures in a

 

hazardous area could result in personal injury or property damage.

To avoid circuit damage when working inside the unit, use appropriate electrostatic discharge precautions, such as wearing a grounded wrist strap.

1.Perform the backup procedure described in “Preserving Configuration and Log Data” in Chapter 6, Troubleshooting.

Note: Removing the battery erases the contents of the ROC827’s RAM.

2.Remove all power from the ROC827.

3.Remove the wire channel cover.

4.Remove the two screws on the CPU faceplate.

5.Remove the CPU faceplate.

6.Remove the CPU (as described in “Removing the CPU Module” in Chapter 2, Installation and Use).

Issued Mar-06

Power Connections

3-25

Page 69
Image 69
Emerson ROC827 instruction manual Replacing the Internal Battery, Replacement Battery Types