Table 3-5. Estimated Power Consumption

Device

Power Consumption (mW)

Quantity

Sub-Total

Description

PTYPICAL

Used

(mW)

 

 

 

 

 

 

CPU and ROC827 Backplane

 

 

 

 

Power Input Module PM-12

110 mA @ 12 volts dc

1320 mW

 

 

Power Input Module PM-24

55 mA @ 24 volts dc

1320 mW

 

 

Per Active LED – Maximum 10

1.5 mA

18 mW

 

 

EIA-232 (RS-232) Module

4 mA @ 12 volts dc

48 mW

 

 

Per Active LED – Maximum 4

1.5 mA

18 mW

 

 

EIA-422/485 (RS-422/485) Module

112 mA @ 12 volts

1344 mW

 

 

Per Active LED – Maximum 2

1.5 mA

18 mW

 

 

Dial-up Modem Module

95 mA @ 12 volts dc

1140 mW

 

 

Per Active LED – Maximum 4

1.5 mA

18 mW

 

 

Expanded Backplanes

 

 

 

 

 

70 mA @ 12 volts dc

840 mW

 

 

 

35 mA @ 24 volts dc

840 mW

 

 

 

 

Total for ROC827 Base Unit

mW

AI Modules

 

Total (from Table 3-6)

 

AO Modules

 

Total (from Table 3-7)

 

 

DI Modules

 

Total (from Table 3-8)

 

 

DO Modules

 

Total (from Table 3-9)

 

 

DOR Modules

 

Total (from Table 3-10)

 

 

PI Modules

 

Total (from Table 3-11)

 

 

MVS Modules

 

Total (from Table 3-12)

 

 

RTD Modules

 

Total (from Table 3-13)

 

 

Thermocouple Modules

 

Total (from Table 3-14)

 

 

HART Modules

 

Total (from Table 3-15)

 

 

 

 

Total for All Modules

mW

 

 

Total for ROC827 Base Unit and All Modules

 

mW

Other Devices

 

Total (from Table 3-16)

 

mW

 

 

Total for ROC827 Base Unit, All Modules, and

mW

 

 

Other Devices

 

 

 

Power System Safety Factor (0.25)

 

mW

 

 

Total for Configured ROC827

mW

Issued Mar-06