![](/images/backgrounds/250286/250286-7926x1.png)
Instruction Manual
Model 755R
Carefully rotate R63 counterclockwise the minimum amount required to obtain energization of ALARM 1 Relay K1 (See Figure
c.To verify correct adjustment of R63, adjust front panel SPAN Control so that the display or re- corder reads 99% of fullscale. Relay K1 should now be
5.Adjust ALARM 2 control function as follows:
a.With ALARM 2 Setpoint Adjust- ment at 100% (i.e., Position 10 on the dial), adjust front panel SPAN Control so that
A.Typical ALARM 1 Setting
|
|
| 40 |
|
|
| |
|
|
| INPUT SIGNAL |
|
|
| Percent of Fullscale |
DEADBAND SET FOR | 30 | ||
20% OF FULLSCALE | |||
|
|
|
|
20
B. Typical ALARM 2 Setting
55
|
|
| INPUT SIGNAL | |
|
|
| Percent of Fullscale | |
DEADBAND SET FOR | ||||
50 | ||||
10% OF FULLSCALE | ||||
| ||||
|
|
| 45 | |
|
|
| ||
|
|
|
b.the display or recorder reads ex- actly fullscale.
c.Set ALARM 2 Calibrate Adjust- ment (R67) to its clockwise limit. Carefully rotate R67 counter- clockwise the minimum amount required to obtain energization of ALARM 2 Relay K2 (See Figure
d.To verify correct adjustment of R67, adjust front panel SPAN Control so that the display or re- corder reads 99% of fullscale. Relay K2 should now be
The ALARM 1 and ALARM 2 Setpoint Adjustments are now properly calibrated and may be used to select the desired alarm setpoints, as described in Section
When input signal moves upscale through this point, the coil of ALARM 1 relay (K1) is energized, providing continuity between the common and
ALARM 1 Setpoint
When input signal moves downscale through this point, the coil of ALARM 1 relay (K1) is
When input signal moves upscale through this point, the coil of ALARM 2 relay (K2) is
ALARM 2 Setpoint
When input signal moves upscale through this point, the coil of ALARM 2 relay (K2) is energized, providing continuity between the common and
Figure
Installation | Rosemount Analytical Inc. A Division of Emerson Process Management |