25613-0-0309Page 14
To Use the Vent Graph (Figure 17)
1. Determine the height of the center of the horizontal vent
pipe. Using this dimension on the Sidewall Vent Graph,
locate the point it intersects with the slanted graph
line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the oor of the unit is 35 feet,
the horizontal run to the outer wall ange must not exceed
6.5 feet.
EXAMPLE B:
If the vertical dimension from the oor of the unit is 6.5
feet, the horizontal run to the outer wall ange must not
exceed 14.5 feet.
Special Note: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be
reduced by 18" (45cm). This does not apply if the 45 degree
elbows are installed on the vertical part of the vent system.
Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal
vent length is 20' and if two 45 degree elbows are required
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per
side wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
Note: On vertical venting the rst elbow does not get
counted.
Note: Flue heat shi eld must be in stalled for v enting
applications with less than two feet of vertical pipe off the
top of the replace.
Figure 17
Acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.

Venting Graph (Dimensions in Feet)

VENTING FIREPLACE - TOP
TOPEXIT-VERTICAL AND HORIZONTALTERMINATION
(DIMENSIONSIN FEET)
VERTICALDIMENSION FROM THE BOTTOM OF THE UNIT
TOTHE CENTER OF THE FLUE OUTLET
WITHVERTICAL OR HORIZONTAL TERMINATIONCAPS
TOPVENT
CONNECTION
HORIZONTALRUN
FLUEHEAT
SHIELD
REQUIRED