Enviro C-10794 owner manual Trouble Shooting, Problem, Possible Cause, Solution

Models: C-10794

1 45
Download 45 pages 19.59 Kb
Page 37
Image 37
Trouble Shooting

Trouble Shooting

Problem

Possible Cause

Solution

Spark will not light

Defective piezo ignitor.

• Check connections to ignitor.

the pilot after

 

• If ignitor connections are good but no spark,

repeatedly pressing

 

replace ignitor.

the spark ignitor

 

 

Broken spark electrode.

• Check for broken ceramic insulation.

 

 

• Replace electrode if broken.

 

Low battery or bad

• Replace the electronic module.

 

electronic module.

• Replace the battery in module.

 

Misaligned spark

• If spark is not arcing from electrode to pilot - adjust

 

electrode.

by loosening the screws on the pilot base. Adjust

 

 

away from burner and retighten.

 

 

 

Pilot will not remain

Problem with

• Check for proper connection of the thermocouple to

lit

thermocouple circuit.

the rear of the valve. If loose, fully tighten lightly.

 

 

• Check pilot for full flame impingement around

 

 

thermocouple. If flame is too small, check gas

 

 

pressure, adjust pilot rate screw, check pilot head for

 

 

damage or blockage.

 

 

• Check thermocouple voltage at rear of valve.

 

 

It must be greater than 7 mV. If low, replace

 

 

thermocouple.

 

Air in gas line (pilot

• Bleed line.

 

dies while knob is

• Check gas line pressure.

 

depressed).

• Contact dealer.

Burners will not

Problem with

• Check gas line pressure .

remain lit

thermopile circuit.

• Check for flame impingement on thermopile. If low,

 

 

see “Pilot will not remain lit”.

 

 

• Check thermopile for minimum of 200 mV when

 

 

burner is switched on.

 

 

• Check wiring to thermostat for breaks.

Flame lifting

Leak in vent pipe.

• Check for leaks in vent connections.

 

 

 

 

Improper vent

• Check vent configuration with manual.

 

configuration.

 

 

 

 

 

Terminal may be

• Check to see if terminal is on correctly.

 

recirculating flue gases.

• May need to install high wind termination cap.

 

 

• Contact dealer.

 

 

 

 

Improperly set vent

• See venting section for proper restrictor setting.

 

restrictor plate.

 

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

 

**Due to additives in gas, glass may get hazy during operation** Clean as

 

needed.

 

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

 

 

 

Flames are burning

Flame impingement

• Check log positioning.

“dirty” or sooting

 

• Check vent restrictor for proper setting.

 

 

• Increase primary air by opening venturi shutter.

 

 

• See also “Burners will not remain lit.”

 

 

 

37

Page 37
Image 37
Enviro C-10794 owner manual Trouble Shooting, Problem, Possible Cause, Solution