Enviro C-10794 Gas Line Connection, To Test Valve Pressures, Natural Gas, Propane, Main Burner

Models: C-10794

1 45
Download 45 pages 19.59 Kb
Page 31
Image 31
GAS LINE CONNECTION

Initial Installation

QUALIFIED INSTALLERS ONLY

GAS LINE CONNECTION AND TESTING:

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

GAS LINE CONNECTION

This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a 3⁄8” male NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI Z223.1.

The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.

 

 

Manifold

 

 

Inlet

 

 

 

 

Pressure Tap

 

Pressure Tap

 

 

 

 

TP TH

 

OUT

 

IN

 

 

 

 

 

 

TP

H

O

 

 

 

I

L

 

OF

 

 

 

 

 

 

 

 

 

F

 

 

 

 

 

P

TH

 

 

 

I

 

 

 

L

 

 

 

T

O

 

 

 

 

 

 

 

 

NO

 

T

P

 

 

 

 

I

 

 

 

 

OL

 

 

 

 

 

Pilot Adjustment

Hi/Low

 

Gas Control

Screw

Knob

 

 

Knob

Figure 44: Fully Labeled Gas Valve.

The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds 1⁄2 PSIG (3.45 KPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1⁄2 psig (3.45 KPa).

Always check for gas leaks with a soap and water solution after completing the required pressure test.

TO TEST VALVE PRESSURES

The pressure taps are located on the left side of the valve

Turn set screw 1 turn counter clockwise to loosen,

Place 5/16” (8 mm) I.D. hose over pressure tap system.

Check pressures using a manometer.

When finished, release pressure, remove hose & tighten set screw.

Table 6: Pressure and BTU Information.

 

Natural Gas

Propane

 

 

 

Main Burner

#39 DMS

#53 DMS

 

 

 

Manifold Pressure

3.8” W.C. / 0.95KPa

11.0” W.C. / 2.7KPa

 

 

 

Min. Manifold Pressure

1.1” W.C. / 0.27KPa

2.7” W.C. / 0.67KPa

 

 

 

Max Supply Pressure

7.0” W.C. / 1.74KPa

13.0” W.C. / 3.28KPa

 

 

 

Min. Supply Pressure

5” W.C. / 1.24KPa

12.0” W.C. / 2.98KPa

 

 

 

Max BTU/hr Input

30,000 BTU/hr (8.80KW)

26,500 BTU/hr (7.76KW)

 

 

 

Min. BTU/hr Input

17,000 BTU/hr (4.98 KW)

14,000 BTU/hr (4.10KW)

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

31

Page 31
Image 31
Enviro C-10794 Gas Line Connection, To Test Valve Pressures, Natural Gas, Propane, Main Burner, Manifold Pressure