Enviro C-11253 Initial Installation, Qualified Installers Only, Vertical Vent Cap Underside

Models: C-11253 C-11102 50-1472

1 48
Download 48 pages 33.91 Kb
Page 24
Image 24
Figure 42: Vertical Vent Cap Underside.

Initial Installation

QUALIFIED INSTALLERS ONLY

6.Place a bead of high temperature silicone on the intake collar of the fireplace, slide the Ø2” (51mm) flex intake liner over the collar, secure the flex liner with three (3) sheet metal screws evenly spaced.

7.At the top of the chimney, apply a bead of Mill-Pac Black sealant to the Ø3” (76mm) pipe of the vent terminal (refer to Figure 42). Slide the flex liner onto the vent terminal and secure with three (3) sheet metal screws evenly spaced.

8.Place a bead of high temperature silicone on the intake collar of the vent terminal (refer to Figure 42). Slide the Ø2” (51mm) flex intake liner over the collar, secure the flex liner with three (3) sheet metal screws evenly spaced.

9.Make a tight connection between the gas fireplace insert flue collar and the fireplace chimney at the top of the chimney. Secure the vent terminal to the chimney using adequate sealant, and according to local building codes.

10.Light the Sonnet and ensure proper operation and proper flame appearance. The amount of air to the venturi may need to be adjusted using the rod under the firebox (see Figure 8). Also refer to Figure 79 for a flame appearance picture.

3" (76mm) Exhaust

2" (51mm) Air Inlet

Figure 42: Vertical Vent Cap Underside.

Figure 43: Installation of Sonnet DV .Manual backgroundManual backgroundManual backgroundManual background The height for the vent must be between 10ft (3.05m) and 35ft (10.67m).

Manual backgroundInstall sealed Vertical Vent Cap to prevent leakage of room air up through Manual backgroundManual background chimney.

The intake is 2" (51mm) and the exhaust is 3" (76mm).

Measure the height of the chimney beforehand and purchase the appropriate kit. Never attempt to over-stretch a flexible liner to accommodate the height of the chimney. Any chimney over 15' (4.6m), install the Sonnet 15’ 2” & 3” Flex Vent (part #50-1512) and the Sonnet 2” & 3” Flex Couplers (part #50-1513). Every joint in the venting must be secured with three (3) #8 x 3/8” HWH sheet metal screws and an appropriate sealant (either silicone or milpac).

The flue damper can be fully blocked open or removed for installation of

the Sonnet; the smoke shelves, shields and baffles may be removed if

attached by mechanical fasteners.

The chimney must be clean, in good working order and constructed of non-combustible materials.

Make sure that all chimney cleanouts are tight fitting and will not permit air to leak into the chimney.

Refractory, glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing the Sonnet.

Figure 43: Installation of Sonnet DV .

24

Page 24
Image 24
Enviro C-11253 Initial Installation, Qualified Installers Only, Vertical Vent Cap Underside, Installation of Sonnet DV