D is turbance | Caus e | Trouble | R e me dy |
| O il present in system | Q uestion user about mode | Let unit stand for several |
| after horizontal | of transportation and time | hours at warm |
| transport. | interval between | temperature and try to |
|
| installation and | start again. If compressor |
|
|
| does not start, open the |
|
|
| system and blow through |
|
|
| with N 2. |
| Locked rotor (fault in | C heck that compressor | If system (filter) is not |
| compressor). | hums and picks up total | blocked, replace |
|
| starting current. O pen | compressor. |
|
| system and blow N 2 |
|
|
| through system. |
|
|
|
|
|
| Ambient temperature | Measure ambient | Find a better location for |
| very low. O il in | temperature. Measure | unit. C ondenser can be |
| compressor too cold, | voltage. | insulated if necessary, but |
| possibly in connection |
| DO N ’T FO RGET to |
| with undervoltage. |
| remove again if ambient |
|
|
| temperature increases. |
|
|
|
|
C ompressor tries to | C an be normal. | Measure the temperature | Find a better location for |
start but does not | Ventilation is perhaps | of compressor housing | the unit.arrange ways for |
always succeed on | insufficient. | (max. 110°C ) and filter | a better ventistat. |
first attempt. |
| (max. 70°C ). |
|
|
|
|
|
Refrigerate and/or | Standstill time for | C heck for snug fit of | If standstill time is too |
freeze normally. | compressor is too | doors. Time standstill | short, replace thermostat. |
C ompressor tries to | short. | period for compressor. |
|
start but does not |
|
|
|
succeed on first |
|
|
|
attempt. |
|
|
|
C ompressor runs | Thermostat phial is | C heck location of phial. | C orrect the fault. C utout |
continuously. Unit | incorrectly installed. |
| temperature can be raised |
refrigerates/freezes |
|
| by giving the phial a |
normally or too much. |
|
| greater surface contact |
|
|
| with the evaporator. |
|
|
|
|
| Ice formation around | C heck for snug fit of | Inform user to defrost |
| thermostat phial. | doors | unit. |
|
|
|
|
| Thermostat set too | Turn thermostat knob | If compressor stops, |
| low. | inform user about function | |
|
|
| of thermostat. |
| Ice formation in phial |
| Defrost unit. Remove |
| tube. |
| thermostat phial, dry |
|
|
| thoroughly and replace. |
To be continued on |
|
| Repeat until the phial is |
the next page. |
|
| dry. Seal with putty. |
4.