4Configuration Menu

Column 1 = System Up Time.

Column 2 = Modbus Master Register Number.

Column 3 = Direction of Packet: OUT = Packet Sent from the F3400/F1000 (Master Request). Column 4 = Modbus Packet.

4.10.4 Reset Modbus Port

This link allows users to reset the Modbus port so that the contents of the polling registers will be cleared.

4.10.5 F-Series Modbus Slave Register Map

Table 4.1 Output Registers

Register

Description

Range

 

 

 

40001-40032

Input #1-32 Value

0-65535

 

 

 

40033-40187

Reserved

 

 

 

 

40188-40193

MAC Address

0-65535

 

 

 

40194-40197

IP Address

0-65535

 

 

 

40198

Model No.

0-65535

 

 

 

40199

Firmware Version

0-65535

 

 

 

40200

Number of Alarms Present

0-65535

 

 

 

40201-40232

Input #1-32 Alarm Bitmap

See Table 4.2

 

 

 

40233-40400

Reserved

 

 

 

 

40401-40432

Input #1-32 Configuration

See Table 4.3

 

 

 

Table 4.2 Status Flags (Registers 40201-40232)

 

 

 

 

Bit

Description

 

 

 

 

 

00

1

= High1 Alarm

 

 

 

 

 

01

1

= Low1 Alarm

 

 

 

 

 

02

1

= High2 Alarm

 

 

 

 

 

03

1

= Low2 Alarm

 

 

 

 

 

04

1

= Digital Alarm

 

 

 

 

Table 4.3 Status Flags (Registers 40401-40432)

 

 

 

 

Integer

Description

 

 

 

 

 

0Not Installed

1Not Configured