A P P E N D I X

ANALOG INPUT 4-20MA REFERENCE

CHART

Analog 4-20Ma Gain/Offset Conversion Formula:

Gain = Sensor Range (High Value - Low Value) / 4

Offset = Sensor Low Value - Gain

Example: TH140 Humidity

Gain = (High Value (100) -Low Value (0)) / 4 = 25

Offset = (Sensor Low Value (0) - Gain (25)) = -25

Table A.1 Analog Input 4-20mA Reference Chart

RLE

 

 

 

 

Product

Transducer Type

Range

Gain

Offset

Number

TEMPERATURE

 

 

 

 

 

 

 

 

TH140

Temperature (Display in Deg F)

50°F - 95°F

11

39

 

 

 

 

 

 

Temperature (Display in Deg F

32°F - 122°F

22

11

 

 

 

 

 

 

Temperature (Display in Deg C)

10°C - 35°C

6

4

 

 

 

 

 

 

Temperature (Display in Deg C

0°C - 55°C

13

-13

 

 

 

 

 

 

Humidity

0% - 100% RH

25

-25

 

 

 

 

 

T120

Temperature (Display in Deg F)

50°F - 95°F

11

39

 

 

 

 

 

 

Temperature (Display in Deg F)

32°F - 122°F

22

11

 

 

 

 

 

 

Temperature (Display in Deg C)

10°C - 35°C

6

4

 

 

 

 

 

 

Temperature (Display in Deg C)

0°C - 50°C

13

-13

 

 

 

 

 

CURRENT

 

 

 

 

 

 

 

 

 

CT55

Current

0 - 5 Amps

1

-1

 

 

0 - 55 Amps

13

-13

 

 

 

 

 

www.rletech.com

79

970.484.6510

Page 79
Image 79
Falcon F3400, F1000 manual Analog Input 4-20MA Reference Chart, Analog 4-20Ma Gain/Offset Conversion Formula