4Configuration Menu
Example: Temperature sensor with a sensing range of
Gain =
Offset = 50 - 11 = 39
Example: Temperature sensor with a sensing range of
Convert
Gain =
Offset = 10 - 6 = 4
Example: Humidity sensor with a range of 0 - 100% RH
Gain =
Offset = 0 - 25 =
High Limit 2: Applies only when the input type is Analog
High Limit 1: Applies only when the input type is set for Analog
Low Limit 1: Applies only when the input type is Analog
Low Limit 2: Applies only when the input type is Analog
Unit Of Measure (UOM): The 10 character field used to assign a unit of measure label to analog values, such as °F, °C, % RH, Amps, Volts, PSI, etc. The unit of measure field is only required when the input type is Analog
Alarm Label: Used for input identification. Applies to all input types except “Not Configured”. For Analog input types, this label is displayed on the F3400/F1000 Main Menu and the Input Configuration Menu. When the input alarms and/or returns to normal, the label is included in the Alarm History and notification messages. For Digital NO and Digital NC inputs, the label is displayed on the F3400/F1000 Main Menu, Input Configuration Menu, Alarm History page and in notification messages only when the device is in alarm. For Digital Status inputs, the label is displayed on the F3400/F1000 Main Menu when the input is on. When the input turns on, the label is also included in the Digital Status History.
Normal Label: Applies to input types Digital NO, Digital NC and Digital Status. This field may be left blank. If it is left blank, the F3400/F1000 displays the Label (from above). This label is displayed on the main page when the input is normal, in the Alarm History when the input returns to normal and in notification messages. For Digital Status inputs, the label is displayed on the main page when the input is off. When the input turns off, the label is also included in the Digital Status History.
www.rletech.com | 38 | 970.484.6510 |