Ruinet Utility User Manual
Page 18 of 46
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Parameter Description
Connection The current connection being displayed out of the total number
TX bytes Number of bytes sent.
TX packets Number of packets sent.
TX dropped Number of packets not sent for reasons that include the transmit buffers
being full.
TX errors Errors during transmission such as hardware errors.
RX IP fragments The number of IP fragmented packets received.
Collisions Number of collisions - the network is too busy.
TX abort errors
TX carrier errors
TX heartbeat errors
TX window errors
The NIC layer reports this error. Should be zero.
Max TX buffers used The highest value for the used transmit buffer count since the
FieldServer was restarted. An extremely busy network may have a max
of 7 or 8 but values this high are generally not expected.
Tx buffers in use Current transmit buffers in use.
Tx broadcast The number of broadcast messages sent.
RX bytes Number of bytes received by the API.
RX pkts total Number of packets received by the API.
RX pkts for us The number of received packets destined for transmission.
RX pkts NOT for us The number of received packets destined for transmission not meant for
the API.
RX dropped The number of received packets which were dropped for reasons such
as the Ethernet queue being full.
RX errors
RX length errors
RX overflow errors
RX crc errors
RX frame errors
RX frame errors
RX buffer full
RX ring buffer error
The NIC layer reports this error. Should be zero.
RX IP type Number of messages using IP protocol received.
RX ARP type Number of messages using ARP protocol received.
RX BACNET type Number of messages using BACnet protocol received.
RX 802_3 type Number of messages using 802_3 Ethernet protocol received.
RX UNKNOWN type Number of messages using other Ethernet protocol received.
Frag buf overrun IP defrag on the receive side. The buffer is (about 80kb) is full.
RX Broadcast Number of packets received in broadcast.
Exception 1 The Ethernet packet type could not be identified
Exception 2
A
n Ethernet packet received (i.e. addressed to the FieldServer Ethernet
address) was addressed to another IP address - either an Ethernet
broadcast was sent with a specific IP address, or another device has an
incorrect ARP table.
Exception 3
A
UDP packet of length >1500 was received which cannot be handled
by the FieldServer.
Exception 4 The Ethernet TX interrupt handler was kick started.
RX global timeout
RX local timeout This statisticis currently not used.