Finisar AN-2030 specifications F i n i s a r, 1External Calibration

Models: AN-2030

1 35
Download 35 pages 39.34 Kb
Page 19
Image 19
1External Calibration

AN-2030: Digital Diagnostic Monitoring Interface for Optical Transceivers

F i n i s a r

1External Calibration

2Measurements are raw A/D values and must be converted to real units using calibration

3constants stored in EEPROM locations 56 – 95 at 2 wire serial bus address A2h (see

4 Table 3.15). Calibration is valid over specified device operating temperature and

5voltage. Alarm and warning threshold values should be interpreted in the same manner

6as real time 16 bit data.

71) Internally measured transceiver temperature. Module temperature, T, is given by the

8following equation: T(C) = Tslope * TAD (16 bit signed twos complement value) + Toffset.

9The result is in units of 1/256C, yielding a total range of –128C to +128C. See Table

103.15 for locations of TSLOPE and TOFFSET. Temperature measurement is valid from –

1140°C to +125°C with an accuracy of ± 3°C. The temperature sensor is located in the

12center of the module and is typically 5 to 10 degrees hotter than the module case. See

13Tables 3.12 and 3.13 above for examples of temperature format.

142) Internally measured transceiver supply voltage. Module internal supply voltage, V, is

15given in microvolts by the following equation: V(µV) = VSLOPE * VAD (16 bit unsigned

16integer) + VOFFSET . The result is in units of 100µV, yielding a total range of 0 – 6.55V.

17See Table 3.15 for locations of VSLOPE and VOFFSET . Accuracy is ±100mV.

183) Measured transmitter laser bias current. Module laser bias current, I, is given by the

19following equation: I(µA) = ISLOPE * IAD (16 bit unsigned integer) + IOFFSET . This result is

20in units of 2 µA, yielding a total range of 0 to 131 mA. See Table 3.15 for locations of

21ISLOPE and IOFFSET. Accuracy is ± 10%. Early versions of the digital diagnostic standard

22(SFF-8472) used a scale factor of 1µA/AD Count for interpreting laser bias current

23readings. SFF-8472 later changed the scale factor to the current value of 2µA/AD

24Count. All Finisar modules using a scale factor of 2µA/AD Count have an ASCII “A”

25written in byte 56 of the ‘vendor rev’ field (see table 3.1). Legacy Finisar modules using

26a scale factor of 1µA/AD Count contain either zero or ASCII space (20h) or one of two

27place holders: “X1—“, “1A—“, in location 56.

284) Measured coupled TX output power. Module transmitter coupled output power,

29TX_PWR, is given in µW by the following equation: TX_PWR (µW) = TX_PWRSLOPE *

30TX_PWRAD (16 bit unsigned integer) + TX_PWROFFSET. This result is in units of 0.1µW

31yielding a total range of 0 – 6.5mW. See Table 3.15 for locations of TX_PWRSLOPE and

32 TX_PWROFFSET. Data is factory calibrated to absolute units using the most

33representative fiber output type. Accuracy is ±3dB. Data is not valid when the

34transmitter is disabled.

35

9/26/02 Revision D

Page 19

Page 19
Image 19
Finisar AN-2030 specifications F i n i s a r, 1External Calibration