INSTALLATION

INSTALLATION

PROCEDURES

Transmitter

Refer to the appropriate procedure and the accompanying illustrations

 

when installing the transmitter.

 

Head Mount Transmitter with DIN Plate Style Sensor

 

The least complicated assembly uses:

 

• an integral mount sensor with flying leads

 

• an integral DIN style connection head

 

a standard extension

 

a threaded thermowell

 

Refer to Volume 2 of the Rosemount Sensors Product Data Sheet

 

(document number 00813-0101-2654) for complete sensor and

 

mounting accessory information.

 

To complete the assembly, follow the steps described below.

 

1.

Attach the thermowell to the pipe or process container wall. Install

 

 

and tighten the thermowell before applying pressure.

 

2.

Set the transmitter failure mode switch

 

 

(see Figure 2-13 on page 2-16).

 

3.

Assemble the transmitter to the sensor. Push the transmitter

 

 

mounting screws through the sensor mounting plate and insert the

 

 

snap rings (optional, part number 00644-4432-0001) into the

 

 

groove of each transmitter mounting screw.

 

4.

Insert the transmitter-sensor assembly into the connection head.

 

 

Thread the transmitter mounting screw into the connection head

 

 

mounting holes.

 

5.

Assemble the extension to the connection head. Insert the

 

 

assembly into the thermowell.

 

6.

Attach a cable gland into the shielded cable.

 

7.

Insert the shielded cable leads into the connection head through

 

 

the cable entry. Connect and tighten the cable gland.

 

8.

Connect the shielded cable leads to the transmitter power

 

 

terminals. Avoid contact with leads and terminals.

 

9.

Install and tighten the connection head cover. Enclosure covers

 

 

must be fully engaged to meet explosion-proof requirements.

Figure 2-5. Typical Model 244EH

Mounting Configuration Using Integral

Mount Sensor and Assembly

Model 244EH

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head

 

 

 

 

 

 

 

 

Threaded

Transmitter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermowell

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Integral Mount Sensor

Threaded Extension

with Flying Leads

 

644-0000B04A

2-5