Fisher 244EH, 244ER manual Configuring a Single Transmitter, Configuration Window

Models: 244EH 244ER

1 64
Download 64 pages 54.53 Kb
Page 29
Image 29
Configuring a Single

Configuring a Single

Transmitter

NOTE

See “Configuration Software” on page 2-9for instructions on how to install the configuration software.

To configure a single Model 244EH or 244ER transmitter, perform the following procedure:

1. Disconnect power to the transmitter if the transmitter is installed in a measurement loop.

NOTE

Configuring a transmitter while it is powered in a measurement loop could cause the Model 244EC to shunt the current.

2.Set up the transmitter configuration system (see “Model 244EC Configuration Interface” on page 2-11)and open the program.

3.Select READ FROM XMTR from the menu bar to initiate the transmitter configuration. The main configuration window will appear (see Figure 3-1).

Figure 3-1. Models 244EH and 244ER

Configuration Software Main

Configuration Window

244E-244DF01

4.Set the configuration parameters. To view a complete list of options for each parameter, click the drop-down arrow in any parameter box. For example, on the main configuration screen, click the arrow in the UNITS box to view a list of available units.

NOTE

The configuration of the Intermittent Sensor Detect feature of the Model 244E Temperature Transmitter with version 5.5.1 software cannot be changed with the Model 244EC version 2.0 or earlier. For more information see Section 4: Maintenance and Troubleshooting.