6. Configuration

6. 5. Monitored parameters

It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu ([COMMUNICATION MAP] submenu) on the graphic display terminal.

The selection is made via the [6 – MONITOR CONFIG.] menu ([6.3 - CONFIG. COMM. MAP] submenu).

Each parameter [Address 1 select] ... [Address 4 select] can be used to choose the logic address of the parameter. Select an address of zero to disable the function.

In the example given here, the monitored words are:

Parameter 1 = Motor current (LCr): logic address 3204; signed decimal format

Parameter 2 = Motor torque (Otr): logic address 3205; signed decimal format

Parameter 3 = Last fault occurred (LFt): logic address 7121; hexadecimal format

Disabled parameter: address 0; default format: hexadecimal format

One of the three display formats below can be assigned to each monitored word:

 

RDY

NET

 

+0.00Hz

0A

 

 

 

6.3 CONFIG. COMM. MAP.

 

 

 

 

 

Address 1 select

:

 

 

3204

FORMAT 1

 

:

 

 

Signed

Address 2 select

:

 

 

3205

FORMAT 2

 

:

 

 

Signed

Address 3 select

:

 

 

7121

 

 

 

 

 

 

 

 

 

Code

 

 

 

 

Quick

 

 

 

 

 

 

 

 

 

FORMAT 3

 

:

 

 

Hex

Address 4 select

:

 

 

0

FORMAT 4

 

:

 

 

Hex

Format

Range

Terminal display

Hexadecimal

0000 ... FFFF

[Hex]

 

 

 

Signed decimal

-32,767 ... 32,767

[Signed]

 

 

 

Unsigned decimal

0 ... 65,535

[Unsigned]

 

 

 