Schneider Electric VW3 A3 303 user manual Modbus 2-wire standard schematic, Master

Models: VW3 A3 303

1 47
Download 47 pages 62.02 Kb
Page 40
Image 40

9. Appendix

9. 2. Modbus 2-wire standard schematic

The standard schematic corresponds to the Modbus specification published in 2002 on www.modbus.org (Modbus_over_serial_line_V1.pdf, Nov 2002) and, in particular, to the 2-wire multipoint serial bus schematic.

The Modbus card (VW3 A3 303) conforms to this specification.

Schematic diagram:

Master

 

 

R

G

5 V

 

 

 

650 Ω

650 Ω

 

 

 

0 V

 

D1

 

 

120 Ω

 

120 Ω

1n F

 

1n F

D0

 

 

Common

 

 

R

G

Slave 1

R

G

Slave n

Type of trunk cable

Shielded cable with 1 twisted pair and at least a 3rd conductor

Maximum length of bus

1000 m at 19200 bps with the Telemecanique TSX CSAp00 cable

 

 

Maximum number of stations (without

32 stations, i.e., 31 slaves

repeater)

 

Maximum length of tap links

• 20 m for one tap link

 

• 40 m divided by the number of tap links on a multiple junction box

Bus polarization

• One 450 to 650 Ω pull-up resistor to the 5 V (650 Ω or thereabouts recommended)

 

• One 450 to 650 Ω pull-down resistor to the Common (650 Ω or thereabouts

 

recommended)

 

This polarization is recommended for the master.

Line termination

One 120 Ω 0.25 W resistor in series with a 1nF 10 V capacitor

 

 

Common polarity

Yes (Common), connected to the protective ground at one or more points on the bus

 

 

40