8. Modbus protocol

8. 3. Modbus functions available

The following table indicates which Modbus functions are managed by the Altivar 71 and specifies their limits. The "read" and "write" functions are defined from the point of view of the master.

Code

Modbus name

Description

Broadcast

Size of data

3 = 16#03

Read Holding Registers

Read N output words

NO

63 words, max.

 

 

 

 

 

4 = 16#04

Read Input Registers

Read N input words

NO

63 words, max.

 

 

 

 

 

6 = 16#06

Write Single Register

Write one output word

YES

 

 

 

 

 

 

8 = 16#08

Diagnostics

Diagnostics

NO

 

 

 

 

 

 

11 = 16#0B

Get Comm Event Counter

Read counter

NO

 

 

 

 

 

 

16 = 16#10

Write Multiple Registers

Write N output words

YES

61 words, max.

 

 

 

 

 

23 = 16#17

Read/Write Multiple Registers

Read/write N words

NO

20/20 words max.

 

 

 

 

 

43 = 16#2B

Read Device Identification

Identification

NO

 

 

 

 

 

 

8. 4. Read Holding/Input Registers (3/4)

Functions 3 and 4 access all the drive registers that make no distinction between the "Holding" or "Input" types.

Request:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave no.

03/04

No. of first word

 

Number of words

 

 

CRC16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hi

 

Lo

 

Hi

 

Lo

 

Lo

 

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 byte

1 byte

2 bytes

 

 

 

2 bytes

 

 

2 bytes

 

 

 

 

 

Response:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave no.

03/04

Number of

 

 

First word value

 

-------

 

Last word value

 

 

 

CRC16

 

 

bytes read

 

Hi

 

Lo

 

 

 

Hi

 

 

Lo

 

 

Lo

 

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 byte

1 byte

1 byte

 

2 bytes

 

 

 

 

2 bytes

 

 

 

2 bytes

Example: Use function 3 to read 4 logic address words 3102 to 3105 (16#0C1E to 16#0C21) on slave 2, where:

SFr = Switching frequency = 4 kHz (logic address 3102 = 16#0028)

tFr = Maximum output frequency = 60 Hz (logic address 3103 = 16#0258)

HSP = High speed = 50 Hz (logic address 3104 = 16#01F4)

LSP = Low speed = 0 Hz (logic address 3105 = 16#0000)

Request:

02

03

0C1E

0004

276C

Response:

02

03

08

0028

0258

01F4

0000

52B0

 

 

 

 

 

 

 

 

 

Value of:

 

3102

3103

3104

3105

 

Parameter code:

SFr

tFr

HSP

LSP

 