5. Connecting to the bus
5. 1. Wiring recommendations
•Use
•Keep the Modbus cable away from the power cables (30 cm minimum).
•Be sure to cross the Modbus cable and the power cables at right angles.
•Whenever possible, connect the bus cable shielding to the protective ground, e.g., to the ground of each device if this ground is connected to the protective ground.
•Install a line terminator at both ends of the line.
•Ensure the correct line polarization.
•Connect the common polarity ("Common" signal) to the protective ground at one or more points on the bus.
For more information, please refer to the TSX DG KBL E guide: "Electromagnetic compatibility of industrial networks and fieldbuses".
5. 2. Modbus RS485 standard
The characteristics and accessories mentioned in this section ("5. Connecting to the bus") comply with the Modbus standard. Other
The latest generation of Telemecanique equipment conforms to Modbus
Main characteristics: |
|
|
|
Maximum length of bus | 1000 m at 19,200 bps |
Maximum number of stations | 32 stations, i.e., 31 slaves (without repeater) |
9