6. Configuration

6. 1. Communication parameters

Configure the following parameters in the [1.9 - COMMUNICATION] (COM-)menu, [Uni-Telway/Modbus](UtL-)submenu: [Protocol] (PrO), [Bit rate] (bdr) and [Format] (FOr).

These parameters can only be modified when the motor is stopped. Modifications can only be taken into account by the drive following a power break.

Parameter

Possible values

Terminal display

Default value

[Protocol]

Uni-Telway

[Unitelway] (UtE)

[Unitelway] (UtE)

(PrO)

Modbus/RTU

[Modbus RTU] (rtU)

 

 

Modbus/ASCII

[Modbus ASCII] (ASC)

 

[Address]

0 to 247

[0] (0) to [247] (247)

Value taken from the address switches

(AdrC)

 

 

 

 

 

 

 

[Bit rate]

4800 bps

[4800 Bd] (4 8)

[19.2 Kbps] (19 2)

(Bdr)

9600 bps

[9600 Bd] (9 6)

 

 

19,200 bps

[19200 Bd] (19 2)

 

 

 

 

 

[Format]

In RTU mode only:

 

[8-O-1] (8o1)

(FOr)

8 data bits, odd parity, 1 stop bit

[8-O-1] (8o1)

 

 

8 data bits, even parity, 1 stop bit

[8-E-1] (8E1)

 

 

8 data bits, no parity, 1 stop bit

[8-N-1] (8n1)

 

 

8 data bits, no parity, 2 stop bits

[8-N-2] (8n2)

 

 

In RTU and ASCII modes:

 

 

 

7 data bits, odd parity, 1 stop bit

[7-O-1] (7o1)

 

 

7 data bits, even parity, 1 stop bit

[7-E-1] (7E1)

 

 

7 data bits, odd parity, 2 stop bits

[7-O-2] (7o2)

 

 

7 data bits, even parity, 2 stop bits

[7-E-2] (7E2)

 

14

Page 14
Image 14
Schneider Electric VW3 A3 303 user manual Configuration, Communication parameters