Schneider Electric VW3 A3 303 user manual Configuration

Models: VW3 A3 303

1 47
Download 47 pages 62.02 Kb
Page 17
Image 17

6. Configuration

bControl in Drivecom profile via Modbus and reference switching at the terminals

The command comes from Modbus.

The command comes either from Modbus or from the terminals. Input LI5 at the terminals is used to switch the reference between Modbus and the terminals.

The command is in Drivecom profile.

Configure the following parameters:

Parameter

Value

Comment

Profile

Separate Drivecom profile

The run commands follow the Drivecom profile, and the command and

 

 

reference can come from different channels.

 

 

 

Reference 1 configuration

Network card

Reference 1 comes from Modbus.

 

 

 

Reference 1B configuration

Analog input 1 on the terminals

Reference 1B comes from input AI1 on the terminals.

 

 

 

Reference switching

Input LI5

Input LI5 switches the reference (1 1B).

 

 

 

Command 1 configuration

Network card

Command 1 comes from Modbus.

 

 

 

Command switching

Channel 1

Channel 1 is the command channel.

 

 

 

Note: Reference 1B is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference (summing, PID, etc) are inhibited.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6

- COMMAND] (CtL-)

[Profile] (CHCF)

[Separate] (SEP)

 

 

 

 

 

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

 

 

 

 

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

 

 

 

 

 

[Cmd switching] (CCS)

[ch1 active] (Cd1)

 

 

 

 

[1.7

APPLICATION FUNCT.] (FUn-)

[Ref.1B channel] (Fr1b)

[Ref. AI1] (AI1)

[REFERENCE SWITCH.]

 

 

[Ref 1B switching] (rCb)

[LI5] (LI5)

 

 

 

 

 

 

17

Page 17
Image 17
Schneider Electric VW3 A3 303 user manual Configuration