6. Configuration

6. 3. Communication scanner

The communication scanner enables all the application-relevant parameters to be grouped in 2 consecutive word tables so that single read and write operations may be performed. It is even possible to perform a single transaction using the "Read/Write Multiple Registers" (23 = 16#17) function.

The 8 output variables are assigned using the 8 [Scan.Outp address] (nCAp) parameters. They are configured using the graphic display terminal via the [1.9 - COMMUNICATION] (COM-)menu, [COM. SCANNER OUTPUT] (OCS-)submenu.

The 8 input variables are assigned using the 8 [Scan. INp address] (nMAp) parameters. They are configured using the graphic display terminal via the [1.9 - COMMUNICATION] (COM-)menu, [COM. SCANNER INPUT] (ICS-)submenu.

Enter the logic address of the parameter (see the Parameters Manual).

If a [Scan.Outp address] (nCAp) or [Scan. INp address] (nMAp) parameter equals zero, the corresponding variable is not used by the drive.

These 16 assignment parameters are described in the tables below:

Configuration parameter name

Default assignment of the output variable

[Scan. Out1 address] (nCA1)

Control word (CMd)

 

 

[Scan. Out2 address] (nCA2)

Speed reference (LFrd)

 

 

[Scan. Out3 address] (nCA3)

Not used

 

 

[Scan. Out4 address] (nCA4)

Not used

 

 

[Scan. Out5 address] (nCA5)

Not used

 

 

[Scan. Out6 address] (nCA6)

Not used

 

 

[Scan. Out7 address] (nCA7)

Not used

 

 

[Scan. Out8 address] (nCA8)

Not used

 

 

Configuration parameter name

Default assignment of the input variable

[Scan. IN1 address] (nMA1)

Status word (EtA)

 

 

[Scan. IN2 address] (nMA2)

Output speed (rFrd)

 

 

[Scan. IN3 address] (nMA3)

Not used

 

 

[Scan. IN4 address] (nMA4)

Not used

 

 

[Scan. IN5 address] (nMA5)

Not used

 

 

[Scan. IN6 address] (nMA6)

Not used

 

 

[Scan. IN7 address] (nMA7)

Not used

 

 

[Scan. IN8 address] (nMA8)

Not used

 

 

Example of configuration via the graphic display terminal:

 

RDY

 

NET

 

+0.00Hz

0A

 

 

 

 

 

 

 

COM. SCANNER INPUT

 

 

 

 

 

 

 

Scan. IN1 address

:

 

 

3201

Scan. IN2 address

:

 

 

8604

Scan. IN3 address

:

 

 

0

Scan. IN4 address

:

 

 

0

Scan. IN5 address

:

 

 

0

 

 

 

 

 

 

 

 

 

 

Code

 

 

 

 

Quick

 

 

 

 

 

 

 

 

 

 

Scan. IN6 address

:

 

 

0

Scan. IN7 address

:

 

 

0

Scan. IN8 address

:

 

 

0

 

RDY

 

NET

 

+0.00Hz

0A

 

 

 

 

 

 

 

COM. SCANNER OUTPUT

 

 

 

 

 

 

 

Scan. Out1 address

:

 

 

8501

Scan. Out2 address

:

 

 

8602

Scan. Out3 address

:

 

 

0

Scan. Out4 address

:

 

 

0

Scan. Out5 address

:

 

 

0

 

 

 

 

 

 

 

 

Code

 

 

 

Quick

 

 

 

 

 

 

 

 

 

 

Scan. Out6 address

:

 

 

0

Scan. Out7 address

:

 

 

0

Scan. Out8 address

:

 

 

0

Note:

Any modification to parameters [Scan.Outp address] (nCAp) or [Scan. INp address] (nMAp) must be made with the motor stopped. The master PLC program should be updated to take account of this modification.

18

Page 18
Image 18
Schneider Electric VW3 A3 303 Communication scanner, Example of configuration via the graphic display terminal, Rdy Net