7. Diagnostics

7. 1. Checking the address

On the graphic display terminal or integrated display terminal, check the address that has been coded on the switches using the [Address] (AdrC) parameter in the [1.9 COMMUNICATION] (COM-)menu, [Uni-Telway / Modbus] (UtL-)submenu.

This parameter cannot be modified.

7. 2. LEDs

The Modbus card has 2 LEDs, RUN and ERR, which are visible through the drive cover.

1.1

1.2

1.3

1.4

1.5

2.1 RUN (green)

2.2 ERR (red)

2.3

2.4

2.5

Green RUN

Red ERR

Meaning

 

Corrective action

LED

LED

 

 

 

Off

Off

Drive not operating

Check the power supply.

or turned off

 

 

 

 

 

 

On

On

Drive starting

 

 

On

Off

Normal operation

 

 

 

 

 

 

 

 

Communication fault

• Check the environment (electromagnetic compatibility).

Off

On

Check the wiring.

on the bus

Check that the master is communicating within the time out period

 

 

 

 

 

 

(= 10 s).

 

 

 

 

 

 

 

• Check the environment (electromagnetic compatibility).

 

 

 

Check the communication parameter configuration (protocol, speed,

Off

Flashing

Error on character received

 

format).

• Do not forget that the communication parameter configuration is only

 

 

 

 

 

 

 

taken into account by the drive following a power break.

 

 

 

Check that the slave address is unique.

 

 

 

• Check the environment (electromagnetic compatibility).

 

 

Card fault

• Check the card/drive connection.

Flashing

Off

Check that only one communication card has been installed.

[internal com. link] (ILF)

Check that no more than two option cards have been installed.

 

 

 

 

 

Replace the communication card.

 

 

 

• Inspect or repair the drive.