9. Appendix

9. 5. 2-wire Jbus schematic

Schematic diagram:

Master

R

G

5 V

470 Ω

470 Ω

0 V

L- (B/B')

150Ω

150 Ω

L+ (A/A')

RR

GG

 

Slave 1

Slave n

 

 

 

Type of trunk cable

Cable with 1 shielded twisted pair

 

Maximum length of bus

1,300 m at 19200 bps

 

 

 

 

Maximum number of stations (without

32 stations, i.e., 31 slaves

 

repeater)

 

 

 

 

 

Maximum length of tap links

3 m

 

 

 

 

Bus polarization

One 470 Ω pull-up resistor to the 5 V

 

 

One 470 Ω pull-down resistor to the 0 V

 

 

This polarization is often provided in the master.

 

 

 

Line termination

One 150 Ω resistor

 

 

 

 

Common polarity

No

 

 

 

 