8. Modbus protocol

8. 11. Communication scanner

The communication scanner can be used to enhance application performance. The drive automatically copies non-contiguous parameters to an input table and an output table. Thus, the copy of several non-contiguous parameters can be read or written in a single request (an operation which would normally have required several Modbus requests).

The input table and the output table each contain 8 variables.

Output variables

Logic address

Default assignment

[Com Scan Out1 val.] (nC1)

12 761

= 16#31D9

Control word (CMd)

 

 

 

 

[Com Scan Out2 val.] (nC2)

12 762

= 16#31DA

Speed reference (LFrd)

[Com Scan Out3 val.] (nC3)

12 763

= 16#31DB

Not used

[Com Scan Out4 val.] (nC4)

12 764

= 16#31DC

Not used

 

 

 

 

[Com Scan Out5 val.] (nC5)

12 765

= 16#31DD

Not used

[Com Scan Out6 val.] (nC6)

12 766

= 16#31DE

Not used

[Com Scan Out7 val.] (nC7)

12 767

= 16#31DF

Not used

 

 

 

 

[Com Scan Out8 val.] (nC8)

12 768

= 16#31E0

Not used

Input variables

Logic address

Default assignment

[Com Scan In1 val.] (nM1)

12 741

= 16#31C5

Status word (EtA)

[Com Scan In2 val.] (nM2)

12 742

= 16#31C6

Output speed (rFrd)

 

 

 

 

[Com Scan In3 val.] (nM3)

12 743

= 16#31C7

Not used

[Com Scan In4 val.] (nM4)

12 744

= 16#31C8

Not used

[Com Scan In5 val.] (nM5)

12 745

= 16#31C9

Not used

 

 

 

 

[Com Scan In6 val.] (nM6)

12 746

= 16#31CA

Not used

[Com Scan In7 val.] (nM7)

12 747

= 16#31CB

Not used

[Com Scan In8 val.] (nM8)

12 748

= 16#31CC

Not used

 

 

 

 

The values of these communication scanner variables can be displayed on the graphic display terminal using the

[1.2-MONITORING]menu, [COMMUNICATION MAP] (CMM) submenu (see section "7. Diagnostics - 7.4 Communication scanner").

These parameters can be accessed via all the read and write requests supported by the drive.

There is a marked improvement in performance for the following functions:

Code

Modbus name

Description

Size of data

3 = 16#03

Read Holding Registers

Read N output words

63 words, max.

4 = 16#04

Read Input Registers

Read N input words

63 words, max.

16 = 16#10

Write Multiple Registers

Write N output words

61 words, max.

23 = 16#17

Read/Write Multiple Registers

Read/write N words

20/20 words max.

43 = 16#2B

Read Device Identification

Identification

 