Image 19

6. Configuration

6. 4. Communication faults

A Modbus fault is triggered if the Modbus card does not receive any Modbus requests at its address within a predefined time period (time out). All Modbus request types are taken into account (read, write, etc.). The time out is fixed at 10 s (non-modifiable).

The response of the drive in the event of a Modbus communication fault can be configured.

Configuration can be performed using the graphic display terminal or integrated display terminal using the [Network fault mgt] (CLL) parameter in the [1.8 FAULT MANAGEMENT] (FLt-)menu, [COM. FAULT MANAGEMENT] (CLL-)submenu.

 

RDY

NET

 

+0.00Hz

0A

 

 

 

COM. FAULT MANAGEMENT

 

 

 

 

 

Network fault mgt

:

 

 

Freewheel

CANopen fault mgt

:

 

 

Freewheel

Modbus fault mgt

:

 

 

Freewheel

 

 

 

 

 

 

 

 

 

Code

 

 

 

 

Quick

 

 

 

 

 

 

 

 

 

The values of the [Network fault mgt] (CLL) parameter, which trigger a [Com. network] (CnF) drive fault, are:

Value

Meaning

 

 

[Freewheel] (YES)

Freewheel stop (factory setting)

 

 

[Ramp stop] (rMP)

Stop on ramp

 

 

[Fast stop] (FSt)

Fast stop

 

 

[DC injection] (dCI)

DC injection stop

 

 

The values of the [Network fault mgt] (CLL) parameter, which do not trigger a drive fault, are:

Value

Meaning

 

 

[Ignore] (nO)

Fault ignored

 

 

[Per STT] (Stt)

Stop according to configuration of [Type of stop] (Stt).

 

 

[fallback spd] (LFF)

Switch to fallback speed, maintained as long as the fault is present and the run command is not disabled.

 

 

[Spd maint.] (rLS)

The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run

command has not been removed.

 

 

 

The fallback speed can be configured via the [Fallback speed] (LFF) parameter in the [1.8 – FAULT MANAGEMENT] (FLt-)menu.

19

Page 19
Image 19