7. Diagnostics

7. 4. Communication scanner

On the graphic display terminal, in the [1.2 - MONITORING] (SUP-)menu ([COMMUNICATION MAP] (CMM-)submenu):

-The [COM. SCANNER INPUT MAP] (ISA-)submenu is used to display the value of the 8 communication scanner input variables [Com Scan Inp val.] (NMp).

-The [COM SCAN OUTPUT MAP] (OSA-)submenu is used to display the value of the 8 communication scanner output variables [Com Scan Outp val.] (NCp).

Input variable

Scanner parameter

No. 1

[Com Scan In1 val.] (NM1)

No. 2

[Com Scan In2 val.] (NM2)

No. 3

[Com Scan In3 val.] (NM3)

No. 4

[Com Scan In4 val.] (NM4)

No. 5

[Com Scan In5 val.] (NM5)

No. 6

[Com Scan In6 val.] (NM6)

No. 7

[Com Scan In7 val.] (NM7)

No. 8

[Com Scan In8 val.] (NM8)

Output variable

Scanner parameter

No. 1

[Com Scan Out1 val.] (NC1)

No. 2

[Com Scan Out2 val.] (NC2)

No. 3

[Com Scan Out3 val.] (NC3)

No. 4

[Com Scan Out4 val.] (NC4)

No. 5

[Com Scan Out5 val.] (NC5)

No. 6

[Com Scan Out6 val.] (NC6)

No. 7

[Com Scan Out7 val.] (NC7)

No. 8

[Com Scan Out8 val.] (NC8)

Configuration of these variables is described in the "Configuration" section.

Example of communication scanner display on the graphic display terminal:

RUN

 

NET

 

+50.00Hz

80A

 

 

 

 

 

 

 

COM. SCANNER INPUT MAP

 

 

 

 

 

 

 

Com Scan In1 val.

:

 

 

34359

Com Scan In2 val.

:

 

 

600

Com Scan In3 val.

:

 

 

0

Com Scan In4 val.

:

 

 

0

Com Scan In5 val.

:

 

 

0

 

 

 

 

 

 

 

Code

 

 

 

Quick

 

 

 

 

 

 

 

 

 

Com Scan In6 val.

:

 

 

0

Com Scan In7 val.

:

 

 

0

Com Scan In8 val.

:

 

 

0

RUN

 

NET

 

+50.00Hz

80A

 

 

 

 

 

 

 

COM SCAN OUTPUT MAP

 

 

 

 

 

 

 

Com Scan Out1 val.

:

 

 

15

Com Scan Out2 val.

:

 

 

598

Com Scan Out3 val.

:

 

 

0

Com Scan Out4 val.

:

 

 

0

Com Scan Out5 val.

:

 

 

0

 

 

 

 

 

 

 

Code

 

 

 

Quick

 

 

 

 

 

 

 

 

 

Com Scan Out6 val.

:

 

 

0

Com Scan Out7 val.

:

 

 

0

Com Scan Out8 val.

:

 

 

0

In this example, only the first two variables have been configured (default assignment).

[Com Scan In1 val.]

= [34343]

Status word = 34359 = 16#8637

V

Drivecom "Operation enabled" state,

 

 

 

 

reverse operation, speed reached

[Com Scan In2 val.]

= [600]

Output speed = 600

V

600 rpm

[Com Scan Out1 val.]

= [15]

Control word = 15 = 16#000F

V

"Enable operation" (Run) command

[Com Scan Out2 val.]

= [598]

Speed reference = 600

V

598 rpm

23