Network Technologies ST-xU operation manual Configuration via OSD, Unit Address and Loop Back

Models: ST-xU

1 42
Download 42 pages 18.35 Kb
Page 32
Image 32

NTI NODEMUX SERIES UNIVERSAL KVM SWITCH

Unit Address and Loop Back

To allow multiple units to be controlled from a single terminal port, the RS232 control interface is designed to allow "daisy chaining" up to 15 units. By setting the appropriate RS232 dip switches, each unit can be given a unique address (1-15). Then the unit will only respond to commands on the bus if its address is embedded in the command. Use the table below to set the unit address.

DIP SWITCH

 

 

UNIT ADDRESS

8

7

6

5

 

OFF

OFF

OFF

OFF

0 (not valid)

OFF

OFF

OFF

ON

1

OFF

OFF

ON

OFF

2

OFF

OFF

ON

ON

3

OFF

ON

OFF

OFF

4

OFF

ON

OFF

ON

5

OFF

ON

ON

OFF

6

OFF

ON

ON

ON

7

ON

OFF

OFF

OFF

8

ON

OFF

OFF

ON

9

ON

OFF

ON

OFF

10

ON

OFF

ON

ON

11

ON

ON

OFF

OFF

12

ON

ON

OFF

ON

13

ON

ON

ON

OFF

14

ON

ON

ON

ON

15

Note: The "loop back" RS232 dip switch (RS232 dip switch 1) should be ON for the last unit in the chain, and OFF for all other units. If only one unit is being controlled, the loop back dip switch should be left ON.

Configuration via OSD

Baud Rate

In order for a terminal to communicate with the NODEMUX, the terminal and NODEMUX must each be configured for the same baud rate.

Press <W> from the Administration Mode menu (page 15) to enter Switch Configuration mode. (Fig. 31) Press <Tab> once to move the cursor bar to highlight "RS232 BAUD RATE". The default setting is 9600.

Press < > (up arrow) or < > (down arrow) to change the selected baud rate to 300,600,1200,2400,4800, or back to 9600.

Be careful with this field. If changed to SLAVE, OSD will not work after power cycling.

Figure 31- Switch Configuration Mode screen

In the event the setting is changed from "stand alone" to "slave", when the switch is power cycled the OSD menu will no longer work. To restore the setting back to "stand alone", factory default settings must be restored via a terminal connected to the RS232 control port. See the RS232 Command "CF" on page 30 to restore default settings.

28

Page 32
Image 32
Network Technologies ST-xU operation manual Configuration via OSD, Unit Address and Loop Back