Power connection and configuration

Figure 16: Redundant FortiGate-5053 power converter trays and 2 + 1 redundant FortiGate-5140 power supplies

Slot 3

Slot 2

Slot 1

Slot 3

Slot 2

Slot 1

2FortiGate-5053 power convertor trays

6FortiGate-5140 power supplies

2 x 1200W = 2400W

5140

5140SAP

2 + 1 redundancy

2 x 1200W = 2400W 2 + 1 redundancy

1FortiGate-5140 chassis

13

11

 

9

 

7

 

5

 

3

1

2

4

 

6

 

8

 

10

 

12

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

FILTER

0 FAN TRAY

1 FAN TRAY

2 FAN TRAY

Connecting a FortiGate-5140 chassis to the FortiGate-5053 power converter tray

To use a FortiGate-5053 power converter tray with the FortiGate-5140 chassis you need to make DC power connections between the FortiGate-5140 chassis and the FortiGate- 5053 power converter tray. You also need to the connect the FortiGate-5140 chassis to data center ground.

Each FortiGate-5140 PEM includes 4 connectors that connect power to 4 different power zones in the FortiGate-5140 chassis. Each power zone supplies power to different FortiGate-5140 slots and cooling fan trays. You should always connect all 4 power zones.

To connect a FortiGate-5140 PEM to a FortiGate-5053 power converter tray

The following procedure describes how to connect power to PEM A. You can repeat this procedure to connect PEM B.

You need the following tools and equipment to connect a FortiGate-5140 PEM to a FortiGate-5053 power converter tray:

A number 2 Phillips screwdriver.

An electrostatic discharge (ESD) preventive wrist or ankle strap with connection cord.

Four black AWG-14 stranded wires with terminal lugs attached and labelled -48V

Four red AWG-14 stranded wires with terminal lugs attached and labelled RTN

A FortiGate-5053 power converter tray containing two or three FortiGate-5140 power supplies and mounted in a rack near the FortiGate-5140 chassis.

Caution: The FortiGate-5053 power convertor tray should not be connected to AC power until specified in the following procedure.

FortiGate-5140-R Chassis Guide

 

01-30000-87705-20090108

25