Shelf manager command line interface (CLI)

FortiGate-5140 chassis

Figure 6: The telco alarm connector (DB-15 male)

 

 

15

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

8

 

 

 

 

Table 5: Telco alarm connector pin assignment

 

 

 

 

 

 

 

 

Pin

 

 

Name

 

 

 

Description

 

 

 

 

 

 

 

 

1

 

 

AMIR+

 

 

 

MinorReset+

 

 

 

 

 

 

 

 

2

 

 

AMIR-

 

 

 

MinorReset-

 

 

 

 

 

 

 

 

3

 

 

AMAR+

 

 

 

MajorReset+

 

 

 

 

 

 

 

 

4

 

 

AMAR-

 

 

 

MajorReset-

 

 

 

 

 

 

 

 

5

 

 

ACNO

 

 

 

CriticalAlarm - NO

 

 

 

 

 

 

 

 

6

 

 

ACNC

 

 

 

CriticalAlarm - NC

 

 

 

 

 

 

 

 

7

 

 

ACCOM

 

 

 

CriticalAlarm - COM

 

 

 

 

 

 

 

 

8

 

 

AMINO

 

 

 

MinorAlarm -NO

 

 

 

 

 

 

 

 

9

 

 

AMINC

 

 

 

MinorAlarm - NC

 

 

 

 

 

 

 

 

10

 

 

AMINCOM

 

 

 

MinorAlarm - COM

 

 

 

 

 

 

 

 

11

 

 

AMANO

 

 

 

MajorAlarm - NO

 

 

 

 

 

 

 

 

12

 

 

AMANC

 

 

 

MajorAlarm - NC

 

 

 

 

 

 

 

 

13

 

 

AMACOM

 

 

 

MajorAlarm - COM

 

 

 

 

 

 

 

 

14

 

 

APRCO

 

 

 

PwrAlarm - NO

 

 

 

 

 

 

 

 

15

 

 

APRCOM

 

 

 

PwrAlarm - COM

 

 

 

 

 

 

 

 

Shield

 

 

Shelf-GND

 

 

 

Shelf Ground

 

 

 

 

 

 

 

 

Shelf manager command line interface (CLI)

You can use the shelf manager CLI to communicate with the intelligent management controllers of the chassis, with boards in the chassis, and with the shelf manager itself. The CLI is an IPMI-based set of commands that can be accessed directly or through a higher-level management application or a script. Using the CLI, you can access information about the current state of the chassis including current board population, current sensor values, threshold settings, recent events, and overall chassis health.

Connecting to the shelf manager CLI using a serial port

You can connect to the shelf manager CLI by connecting the console cable supplied with your chassis to a management PC console port and to the appropriate shelf alarm panel serial port. To connect to the primary shelf manager use Serial 1. To connect to the secondary shelf manager use Serial 2.

FortiGate-5140-R Chassis Guide

1201-30000-87705-20090108http://docs.fortinet.com/ Feedback

Page 12
Image 12