FortiGate-5140 chassis

FortiGate-5140 shelf alarm panel

Table 4: FortiGate-5140 shelf alarm panel connectors

Connector

Type

Speed

Protocol

Description

 

 

 

 

 

SERIAL 1

RJ-45

9600 bps,

RS-232

Serial connection to the primary shelf manager

 

 

8/N/1

serial

command line interface.

 

 

 

 

 

SERIAL 2

RJ-45

9600 bps,

RS-232

Serial connection to the secondary shelf

 

 

8/N/1

serial

manager command line interface.

 

 

 

 

 

ALARM

micro

N/A

Telco

The external dry relay Telco alarm interface

 

DB-15

 

Form-c

(48VDC) provides Telco form-c relay

 

male

 

 

connections for minor, major and critical power

 

 

 

 

faults. The cable required to connect to the

 

 

 

 

alarm interface is not supplied by Fortinet.

 

 

 

 

 

Figure 5 shows the connections between the primary and secondary shelf managers and the shelf alarm panel.

Figure 5: Connections between the shelf managers and the shelf alarm panel

5140SAP

SERIAL 1

SERIAL 2

ALARM

Serial Console Interface

RESET

CAL

CRITI

MAJORMINOR USER1 USER2 USER3

CH3

CH0

 

 

I²C-Switch

Buffer

PCA9545

LTC4300

Enable

Master-Only I²C-bus

Serial Console Interface

CH3

CH0

 

 

I²C-Switch

Buffer

PCA9545

LTC4300

Enable

Master-Only I²C-bus

ShMM-500

ShMM-500

Secondary Shelf Manager (Lower)

Primary Shelf Manager (Upper)

Shelf alarm panel telco alarms

The shelf alarm panel telco alarm interface relay circuits are capable of carrying 60 VDC or 1 A with a max. rating of 30 VA. The shelf alarm panel accepts timed pulse inputs for clearing minor and major alarm states. Reset is accomplished by asserting a voltage differential from 3.3 V to 48 V for between 200 and 300 ms. The acceptance voltage range is from 0 to 48 VDC continuous (handles up to 60 VDC at a 50% duty cycle). The current drawn by a reset input does not exceed 12 mA.

The alarm LED reset button activates the alarm cutoff (ACO) state for major, minor, and user-defined alarms. You cannot reset critical alarms with the alarm LED reset button.

When the ACO state is activated, active alarm LEDs blink and all of the alarm relays are deactivated. The alarm reset button activates the ACO state but does not clear the alarm completely.