Friedrich MR09C1H, MW12C1H, MW09C1H, MR12C1H manual Detail Conditions for Start Controlling

Models: MW12C1H MR09C1H MW09C1H MR12C1H

1 88
Download 88 pages 10.31 Kb
Page 34
Image 34

Function and Control

During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from the indoor unit must be divided into the zones as the followings.)

Detail

Conditions for Start Controlling

Judge the controlling start with the indoor heat exchanger temperature after 2 sec from operation start.

Control in Each Zone

Heat exchanger

 

thermistor temperature

Return/Reset zone

A

Up zone

B

Keep zone

 

C

Drooping zone

D

Stop zone

 

E

 

 

 

34

Page 34
Image 34
Friedrich MR09C1H, MW12C1H, MW09C1H, MR12C1H manual Detail Conditions for Start Controlling