Friedrich MW12C1H, MW09C1H, MR09C1H, MR12C1H manual Evacuation, Procedure

Models: MW12C1H MR09C1H MW09C1H MR12C1H

1 88
Download 88 pages 10.31 Kb
Page 72
Image 72

Troubleshooting

Evacuation

(All amount of refrigerant leaked)

Indoor unit

Liquid side

 

 

 

 

 

Outdoor unit

 

3-Way

 

 

valve

Open

 

 

 

Gas side

 

 

3-Way

 

 

valve

Open

Vacuum pump

 

 

 

Lo

 

OPEN

CLOSE

 

• Procedure

(1)Connect the vacuum pump to the center hose of charge set center hose

(2)Evacuation for approximately one hour.

Confirm that the gauge needle has moved toward -76 cmHg (vacuum of 4 mmHg or less).

(3)Close the valve (Lo side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approxima- tely 5 minutes after turning off the vacuum pump).

(4)Disconnect the charge hose from the vacuum pump.

Vacuum pump oil.

If the vacuum pump oil becomes dirty or depleted, replenish as needed.

72

Page 72
Image 72
Friedrich MW12C1H, MW09C1H, MR09C1H, MR12C1H manual Evacuation, Procedure