Troubleshooting

Mainly detect:

Whether the electronic expansion valve is connected well or not? Is electronic expansion valve damaged? Is refrigerant leaked?

20 minutes after the complete unit is powered off

Is the terminal FA for the

 

 

 

 

 

Connect the

electronic expansion valve

 

 

 

 

 

 

 

 

 

 

wires correctly

 

 

 

 

 

connected correctly?

 

 

 

 

 

 

 

 

 

 

 

Resistances between the first four pins close to the terminal hole and the fifth pin are almost the same, less than 100 ohm.

Replace the electronic expansion valve

If the fault is eliminated?

Replace the control panel AP1

If the fault is eliminated?

Coolant leakage, refilling the coolant

End