COMPONENTS TESTING (continued)

HEATING ELEMENT

All heat pumps and electric heat models are equipped with a heating element with the exception of model YS10M10. The other “YS” and “ES” models are equipped with a 3.3 KW element. The “YM” and “EM” models are equipped with a 4.0 KW element. The “YL” and “EL” models are equipped with a 5.2 KW element.

Heating Element

Sample

The heating element contains a fuse link and a heater limit switch. The fuse link is in series with the power supply and will open and interrupt the power when the temperature reaches 199°F or a short circuit occurs in the heating element. Once the fuse link separates, a new fuse link must be installed.

NOTE: Always replace with the exact replacement. The heater element has a high limit control. This control is a bimetal thermostat mounted in the top of the heating element.

Should the fan motor fail or filter become clogged, the high limit control will open and interrupt power to the heater before reaching an unsafe temperature condition.

The control is designed to open at 110°F ±6°F. Test continuity below 110°F or when it is cooled off.

HEATING ELEMENT (Heat Pump Models)

The heating element for the “Y” model is energized by an outdoor thermistor via the electronic control board. The outdoor defrost thermistor is adjusted at

apredetermined temperature of approximately 30 degrees Fahrenheit and sensed for two consecutive minutes, to stop the compressor and turn on the heating element.

TESTING THE HEATING ELEMENT

WARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

Testing of the elements can be made with an ohmmeter across the terminals after the connecting wires have been removed. A cold resistance reading of approximately 14.5 ohms for the 3.3 KW heater, 11.9 ohms for the 4.0 KW heater and 9.15 ohms for the 5.2 KW heater should be registered.

DRAIN PAN VALVE

During the cooling mode of operation, condensate which collects in the drain pan is picked up by the con- denser fan blade and sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water.

During the heating mode of operation, it is necessary that water be removed to prevent it from freezing during cold outside temperatures. This could cause the con- denser fan blade to freeze in the accumulated water and prevent it from turning.

To provide a means of draining this water, a bellows type drain valve is installed over a drain opening in the base pan.

This valve is temperature sensitive and will open when the outside temperature reaches 40°F. The valve will close gradually as the temperature rises above 40°F to fully close at 60°F.

Bellows Assembly

Drain Pan Valve

33

Page 34
Image 34
Friedrich SM18N30*, SS14N10* Heating Element Heat Pump Models, Testing the Heating Element Electric Shock Hazard

SM18N30*, SS10N10*, SS15N30*, SS12N10*, SS14N10* specifications

Friedrich air conditioners, particularly models SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30*, are renowned for their reliable performance, innovative technologies, and user-friendly features. Designed for both residential and commercial use, these units stand out due to their energy efficiency, advanced cooling capabilities, and versatile operation.

One of the standout features across these models is their energy efficiency. Equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, they help users save on energy costs while reducing their carbon footprint. Specifically, the SS14N10* and SS12N10* models excel in cooling efficiency, ensuring that the spaces they occupy remain comfortably cool even in the hottest conditions. This not only contributes to lower energy bills but also promotes environmental sustainability.

The cooling technologies integrated into these units include advanced inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand of a room. As a result, these air conditioners maintain desired temperatures with minimal fluctuations, ensuring optimal comfort and significant energy savings. Models like SS15N30* and SM18N30* are particularly stellar in maintaining efficiency even during peak usage hours.

Moreover, these air conditioners are equipped with multi-stage filtration systems that enhance indoor air quality. The filters effectively capture dust, allergens, and other pollutants, resulting in cleaner and healthier air for occupants. This is especially important for individuals with allergies or respiratory issues.

User-friendly controls add another layer of convenience. Many models incorporate smart technology allowing users to control the units via mobile apps or home automation systems. This feature enables remote operation, scheduling, and real-time monitoring, making it easier to manage climate conditions effectively.

In terms of design, models like SS10N10* prioritize aesthetics without compromising functionality. They feature sleek, modern designs that seamlessly integrate into various decors, whether in a home or an office. Additionally, quiet operation technology reduces noise levels during functionality, enhancing comfort, particularly in bedrooms or quiet office environments.

Overall, Friedrich’s SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30* models embody the brand's commitment to innovation and customer satisfaction. Their blend of energy efficiency, advanced cooling technology, air quality enhancement, and smart controls positions them as leaders in the air conditioning market, catering to diverse cooling needs while promoting a sustainable future.