Installation Instructions
INSTALL THE DRAIN(S)
An external or an internal drain must be attached to the primary drain connector. A secondary drain is supplied if required by state and local codes. Refer to the local codes for proper installation of the drains. If the secondary drain is not used, seal its drain port with a 3/4” MNPT plug.
External Drain
Attach a 90° PVC elbow to the unit’s female 3/4” NPT drain connector. Use the other end of the elbow to run
a 3/4” Sch. 40 PVC pipe through the knockout holes of both the wall plenum and the architectural louver to the outside. Seal the gap between the plenum hole and PVC tube. See the Installation Instructions in the RAVAL1.
|
|
| Side View |
| ||
Inside wall |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Female drain
fitting 3⁄4”PVC (External drain)
PVC 90° Elbow
Internal Drain
Attach PVC to the unit’s female 3/4” NPT drain connector. See the Installation Instructions in the RAVAL1. Local codes may apply.
|
|
| Side View | |||
Inside wall |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Female drain |
|
fitting 3⁄4” |
|
PVC |
|
(Internal drain) | 19 |
|
DUCTWORK
Prepare the closet ductwork for later connection to the case.
The total flow rate (CFM) and external static pressure (ESP) available can be estimated from the chart below. Use these charts to select your fan speed setting. The
collar on top of the case accepts standard 10” duct.
Pull all duct tight. Extra duct slack can greatly increase static pressure.
NOTICE: Flex duct can collapse and cause airflow restrictions. Do not use flex duct for 90° bends or unsupported runs of 5 ft. or more.
Airflow – CFM @ 230 Volts and @ 265 Volts
|
|
| Indoor Fan CFM |
| ||
|
|
| DUCT SELECT SWITCH |
| ||
|
|
| UP | DOWN | ||
| ESP | High | Medium | Medium | Low | |
| (in. water) | CFM | CFM | CFM | CFM | |
AZ85(H/E)09 | 0.0 | 520 | 460 | 460 | 360 | |
0.1 | 500 | 415 | 415 | 290 | ||
| ||||||
| 0.2 | 480 | 370 | 370 | 220 | |
| 0.3 | 440 | 265 | 265 | - | |
AZ85(H/E)12 | 0.4 | 400 | 160 | 160 | - | |
0.1 | 570 | 465 | 465 | 325 | ||
| ||||||
| 0.2 | 550 | 430 | 430 | 270 | |
| 0.3 | 480 | 345 | 345 | - | |
| 0.4 | 410 | 260 | 260 | - | |
AZ85(H/E)18 | 0.0 | 600 | 520 | 520 | 400 | |
0.1 | 585 | 485 | 485 | 340 | ||
| ||||||
| 0.2 | 570 | 450 | 450 | 280 | |
| 0.3 | 510 | 375 | 375 | - | |
| 0.4 | 450 | 300 | 300 | - |
To correct for 208 volts: 0.91
Your airflow should be balanced based on many factors, such as available ESP, room CFM, and ductwork. Consult an HVAC engineer for proper applications. External static pressure (ESP) can be measured with a manometer or pitot tube. Once this ESP is established, you can calculate the CFM using the above chart.
CFM Recommendations
9,000 BTU | 12,000 BTU | 18,000 BTU | ||||||
390 | 415 | 440 | 440 | 465 | 490 | 435 | 485 | 535 |
| • |
|
| • |
|
| • |
|
• = Recommended Mid Range
Higher CFMs tend to increase Sensible capacity, enhance room circulation and increase duct noise, while lower CFMs tend to increase Latent capacity and reduce noise.