GE 8500 Series Things that are normal, Minute, Delay, Normal Operating Sounds, Silence, “Click”

Models: 8500 Series

1 28
Download 28 pages 10.39 Kb
Page 24
Image 24
Things that are normal.

Instructions

Things that are normal.

Normal Operating Sounds

Safety

Operating Instructions

Care and Cleaning

Troubleshooting Tips

Consumer Support

“CLICK”

-Minute

3

Delay

 

SILENCE

COMPRESSOR PROTECTION

You may hear a pinging noise caused by water being picked up and thrown against the condenser on rainy days or when the humidity is high. This design feature helps remove moisture and improve efficiency.

You may hear relays click when the controls cycle on and off or are adjusted to change the room temperature.

Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip from the outdoor side of the unit.

The indoor fan runs continuously when the unit is operating in the cooling mode, unless the fan switch behind the case front panel is set at fan cycle (up). This will cause the fan to cycle on and off with

the compressor. You may also hear a fan noise stop and start.

You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This is due to a built-in restart protector for the compressor that causes

a 3-minute delay.

During the defrost cycle, both indoor and outdoor fans stop and the compressor will operate in the cooling mode to remove frost from the outdoor coil. After defrost, the unit will restart in electric heat to quickly warm the room to the desired comfort level.

To protect the compressor and prevent short cycling, the unit is designed to run for a minimum of 3 minutes after the compressor starts at any thermostat setting.

24

Page 24
Image 24
GE 8500 Series Things that are normal, Minute, Delay, Normal Operating Sounds, Silence, “Click”, Compressor Protection