Performa 960 FA Control

Performa 960 FA Control

5-Cycle Filter System

Performa

FA

TIME OF DAY

TIME OF REGEN

FACTOR A

FACTOR B

CAPACITY

REGEN TIME

REMAINING

Figure 8

This section covers all aspects of programming the Performa 960 FA control. The control is shipped from the factory with default values for most parameters. These default values will result in a system capacity of

100 gallons (1 cubic meter). While the control may operate with these values, the following parameters must be changed to meet the actual operating conditions, and achieve maximum system capacity and efficiency:

Time of Day

Time of Regeneration

Factor A

Regenerant Dosage

Capacity of the Unit

Refill Controller Value

Regenerant Draw Rate

Slow Rinse Time

Note that some parameters have a single unit of measure option such as the Slow Rinse Time which is only entered in minutes. Other parameters have dual units such as Regenerant Dosage which can be entered in gallons or liters. To select which units are active, look for a comment in the NOTES column of Table 5 and Table 7 on page 14. It will reference another parameter that selects which units are active. For example, parameter P12 (Table 8) selects U.S. units if it is set to “0” and metric if it is set to “1”.

Performa 960 FA Level I Parameters (Table 5)

Level I Parameters are identified as those that have an LED indicator on the front panel. The green indicator illuminates next to the name of the active control setting. The end user has access to all of these parameters. In general, pressing the DOWN ARROW () button displays the Level I Parameters in the following order:

Time of Day

Time of Regeneration

Factor A

Regenerant Dosage

Capacity

If you continue to press the DOWN ARROW () button, the parameters start over with Time of Day. Pressing the UP ARROW () button displays the parameters in reverse order. Refer to Table 5 for a description of these parameters and the available ranges for each parameter.

Press the SET button and the far right digit of the display starts flashing. If you want to change this number, press the UP ARROW () button to increase the number or the DOWN ARROW () button to decrease the number. To skip the number without changing, press the LEFT ARROW () button. When you reach the far left digit, pressing the LEFT ARROW () button will return you to the far right digit .

Note: If you press and hold either the UP ARROW () button or the DOWN ARROW () button for more than one second, the flashing number will increment or decrement at the rate of 10 counts per second.

When the number is correct, press the LEFT ARROW () button. The far right digit stops flashing and the next digit to the left starts flashing. You can only change the flashing number. Continue changing numbers until you reach the desired setting. Press the SET button. The numbers stop flashing and the control accepts the new setting. After approximately 30 seconds, the control starts alternating the display between Time of Day and Capacity.

Note: If the new setting is not accepted because it was outside the allowable range, the old value will be displayed.

12

Page 12
Image 12
GE 960 Series manual Performa 960 FA Control 5-CycleFilter System, Performa 960 FA Level I Parameters Table