Table 3 - Level II Programming Parameters
Parameter |
|
|
|
|
| ||
|
|
|
|
|
|
| |
Name | Description | Range of Values | Minimum | Default | Units of | Notes | |
Increments | Measure | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
P6 | Refill controller | 1 to 99 | 1 | 33 |
| Enter the value molded into the | |
| end of the refill controller. | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
P7 | Regenerant | 1 to 99 | 1 | 25 |
| Select number from Table 4 and | |
draw value |
| enter that number. | |||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
P8 | Not used | NA | NA | NA | NA | NA | |
P9 | Backwash time | 3 to 30 | 1 | 14 | Minutes | Skip this parameter to accept the | |
default or enter a value. | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
P10 | Slow rinse time | 8 to 125 | 1 | 40 | Minutes | Skip this parameter to accept the | |
default or enter a value. | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
P11 | Fast rinse time | 2 to 19 | 1 | 4 | Minutes | Skip this parameter to accept the | |
default or enter a value. | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
| 0 = U.S., 1 = metric. Skip this | |
P12 | Units of Measure | 0 to 1 | 1 | 0 |
| parameter to accept U.S. or enter | |
|
|
|
|
|
| 1 for metric. | |
|
|
|
|
|
|
| |
|
|
|
|
|
| 0 = | |
P13 | Clock mode | 0 to 1 | 1 | 0 |
| 1 = | |
| parameter for a | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
| enter 1 for a | |
|
|
|
|
|
|
| |
| Calendar |
|
|
|
| 0 = no calendar override. Skip this | |
P14 | 0 to 30 | 1 | 0 | Days | parameter for no calendar | ||
override | |||||||
|
|
|
|
| override or enter a value. | ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
| 0 = variable reserve, 1 = fixed | |
|
|
|
|
|
| reserve, 2 = variable reserve with | |
|
|
|
|
|
| immediate regen, | |
P15 | Reserve type | 0 to 3 | 1 | 0 |
| 3 = fixed reserve with immediate | |
|
|
|
|
|
| regen. Skip this parameter to | |
|
|
|
|
|
| accept the default or enter a | |
|
|
|
|
|
| different reserve type. | |
|
|
|
|
|
|
| |
| Fixed reserve |
|
|
|
| Description depends on the value | |
|
|
|
| Percent of | entered for P15. Skip this | ||
P16 | capacity or initial | 0 to 70 | 1 | 30 | |||
capacity | parameter to accept the default or | ||||||
| average value |
|
|
| |||
|
|
|
|
| enter a different value. | ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
P17 | Operation type | 0 to 2 | 1 | 2 |
| 2 = | |
| cocurrent conditioner. | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
| 0 = none, 1 = salt/capacity change | |
P18 | Salt/capacity | 0 to 1 | 1 | 0 |
| locked out. Skip this parameter to | |
change lockout |
| accept the default or enter 1 to | |||||
|
|
|
|
| |||
|
|
|
|
|
| lock out salt/capacity change. | |
|
|
|
|
|
|
| |
|
|
|
|
|
| Loads in a set of default values. | |
P19 | Factory defaults |
| 1 | 99 |
| Refer to the Special Notes for | |
|
| Level II Parameters section in this | |||||
|
|
|
|
|
| ||
|
|
|
|
|
| manual. Do Not Change. | |
|
|
|
|
|
|
|
9