GE 49-7419-2 2INSTALL THE DRAIN, 3DUCTWORK, CFM Recommendations, External Drain, Internal Drain

Models: 49-7419-2 AZ75H18EAC

1 28
Download 28 pages 41.01 Kb
Page 19
Image 19
2INSTALL THE DRAIN

Installation Instructions

2INSTALL THE DRAIN

An external or an internal drain must be attached to the drain connector.

External Drain

Attach a 90° PVC elbow to the unit’s female 3/4″ NPT drain connector. Use the other end of the elbow to run a 3/4″ Sch.40 PVC pipe through the knockout holes of both the wall plenum and the architectural louver to the outside. Seal the gap between the plenum hole and PVC tube. See the Installation Instructions in the RAVAL1.

 

 

 

Side View

Inside wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Female drain

 

 

 

 

 

 

 

 

 

 

fitting 34

 

 

PVC

 

 

 

 

 

(External drain)

 

 

 

 

 

 

 

 

 

 

 

 

PVC

90° Elbow

Internal Drain

Attach PVC to the unit’s female 3/4″ NPT drain connector. See the Installation Instructions in the RAVAL1. Local codes may apply.

Inside wall

Side View

Female drain

fitting 34

PVC External Drain (Internal drain)

3DUCTWORK

Prepare the closet ductwork for later connection to the case.

The total flow rate (CFM) and external static pressure (ESP) available can be estimated from the chart below. Use these charts to select your fan speed setting. The collar on top of the case accepts standard 10″ duct.

Pull all duct tight. Extra duct slack can greatly increase static pressure.

CAUTION: Flex duct can collapse and cause airflow restrictions. Do not use flex duct for 90° bends or unsupported runs of 5 ft. or more.

Airflow – CFM@230 Volts and @ 265 Volts

 

 

 

 

 

Indoor Fan CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DUCT SELECT SWITCH

 

 

 

 

 

 

UP

 

DOWN

 

 

 

 

 

 

 

ESP

High

 

Medium

 

Medium

 

Low

 

 

(in. water)

CFM

 

CFM

 

CFM

 

CFM

 

AZ75(H/E)09

0.0

390

 

340

 

340

 

305

 

 

0.1

370

 

320

 

320

 

290

 

 

 

 

 

 

 

 

 

0.2

350

 

300

 

300

 

270

 

 

 

0.3

330

 

280

 

280

 

250

 

 

 

0.4

310

 

260

 

260

 

230

 

 

AZ75(H/E)12

0.0

475

 

390

 

390

 

350

 

 

0.1

450

 

370

 

370

 

325

 

 

 

 

 

 

 

 

 

0.2

425

 

350

 

350

 

300

 

 

 

0.3

400

 

330

 

330

 

275

 

 

 

0.4

375

 

315

 

315

 

250

 

 

AZ75(H/E)18

0.0

630

 

545

 

545

 

490

 

 

0.1

610

 

530

 

530

 

480

 

 

 

 

 

 

 

 

 

0.2

590

 

515

 

515

 

470

 

 

 

0.3

570

 

495

 

495

 

455

 

 

 

0.4

550

 

475

 

475

 

440

 

To correct for 208 volts: 0.91

Your airflow should be balanced based on many factors, such as available ESP, room CFM, and ductwork. Consult an HVAC engineer for proper applications. External static pressure (ESP) can be measured with a manometer or pitot tube. Once this ESP is established, you can calculate the CFM using the above chart.

CFM Recommendations

9,000 BTU12,000 BTU18,000 BTU

 

 

 

 

 

 

 

 

 

275

300

325

350

375

400

450

500

550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• = Recommended Mid Range

 

 

 

 

Higher CFMs tend to increase Sensible capacity, enhance room circulation and increase duct noise, while lower CFMs tend to increase Latent capacity and reduce noise.

19

Page 19
Image 19
GE 49-7419-2 2INSTALL THE DRAIN, 3DUCTWORK, CFM Recommendations, External Drain, Internal Drain, Installation Instructions