GENEWL

To eliminatethe hward of reaching over heated
surface elements, cabinets or storage spaces
should not be provided over arange.
Hcabinets are provided,the hward can be
reduced by insting arange hood that projects
hotiontily aminimum ofWbeyond the bottom
ofthe cabinets.
men insta~ingthe range between base cabinets,
refer to figure belowfor the stie of the opening
needed. Do not seal the range to cabinets.
CA~ON: men unpacking the range, do not
discard the 4shippingbolts as these are the
levelinglegs.
Ha service cord is used, the wdl receptacle
should be located in accordance with the
dimensions below.
/+
7m=
Y
The figure below shows the recommended
instigation relationship ofthe ranges to the
vertical wallsof the surrounding structure.
Please note the following
N~:
1. The back ofthe range maybe instiled
directiy against the rear wdl ofthe structure.
2. These rangesconform to UL requirements for
“Wspacingfrom the range to adjacent vertical
wallsabove the countertop level.However,to
reduce possiblescorching of verticalWWSand to
tilmke potentialfire hmards under abnormal
surface unit use conditionssuch as high heat or
no pans, aminimumof ~spacing shouldbe
providedon both sides of the cooktop.
3. To eliminatethe hward of reaching over
heated surface units, cabinet storage space
located abovethe surface units should be
avoided.Hacabinet is to be provided, the hward
can be reduced by instilling arange hood that
projects hotiontily aminimum ofWbeyond
the bottom ofthe mbinets.
N~: There is aminimum Vclearance
required from the left side ofthe range to awall.
This clearance is needed to open the left side
oven door or to remove the oven rack.
Not Less Than
-
\\
11+=
DividedCooMop(40” Range) See Note2
30