INSTALLATION
EXTERIOR VENT TERMINAL LOCATIONS
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) B= Clearance to window or door that may be opened *(12"/30cm) C= Clearance to permanently closed window *(min. 12"/30cm) D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of (24"/60cm) from the centerline of the terminal (min. 22"/55cm) check with local code. E= Clearance to unventilated soffit (min. 12"/30cm) F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm), with
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm), with
H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from the centerline of the regulator. J= Clearance to service regulator vent outlet *(min. 36"/90cm) K= Clearance to
Note: * As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances. **A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
***Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
Hampton® | 11 |